GAS PIPE SIZE REQUIRED FOR 1,000 BTU NATURAL GAS
AT 6½ ± 1½ INCH (1.62 ± .37 kPa) WATER COLUMN PRESSURE
|
|
| EQUIVALENT LENGTH |
|
| ||
|
|
|
|
|
|
| |
GAS | 25 FT. | 50 FT. | 75 FT. | 100 FT. | 125 FT. | 150 FT. | |
APPLIANCES | (7.63 m) | (15.25 m) | (22.88 m) | (30.50 m) | (38.13 m) | (45.75 m) | |
TOTAL | |||||||
|
|
|
|
|
| ||
BTU/HR. | BASED ON 0.3" WATER COLUMN PRESSURE DROP FOR LENGTH GIVEN | ||||||
|
|
|
|
|
| ||
100,000 | ¾" (19.05mm) | ¾" (19.05mm) | 1" (2.54cm) | 1" (2.54cm) | 1" (2.54cm) | 1" (2.54cm) | |
120,000 | ¾" (19.05mm) | 1" (2.54cm) | 1" (2.54cm) | 1" (2.54cm) | 1" (2.54cm) | 1" (2.54cm) | |
140,000 | ¾" (19.05mm) | 1" (2.54cm) | 1" (2.54cm) | 1" (2.54cm) | 1" (2.54cm) | 1¼" (3.18cm) | |
160,000 | ¾" (19.05mm) | 1" (2.54cm) | 1" (2.54cm) | 1¼" (3.18cm) | 1¼" (3.18cm) | 1¼" (3.18cm) | |
180,000 | 1" (2.54cm) | 1" (2.54cm) | 1" (2.54cm) | 1¼" (3.18cm) | 1¼" (3.18cm) | 1¼" (3.18cm) | |
200,000 | 1" (2.54cm) | 1" (2.54cm) | 1¼" (3.18cm) | 1¼" (3.18cm) | 1¼" (3.18cm) | 1½" (3.81cm) | |
300,000 | 1" (2.54cm) | 1¼" (3.18cm) | 1¼" (3.18cm) | 1½" (3.81cm) | 1½" (3.81cm) | 1½" (3.81cm) | |
400,000 | 1¼" (3.18cm) | 1¼" (3.18cm) | 1½" (3.81cm) | 1½" (3.81cm) | 1½" (3.81cm) | 2" (5.08cm) | |
500,000 | 1¼" (3.18cm) | 1½" (3.81cm) | 1½" (3.81cm) | 2" (5.08cm) | 2" (5.08cm) | 2" (5.08cm) | |
600,000 | 1½" (3.81cm) | 1½" (3.81cm) | 2" (5.08cm) | 2" (5.08cm) | 2" (5.08cm) | 2" (5.08cm) | |
700,000 | 1½" (3.81cm) | 2" (5.08cm) | 2" (5.08cm) | 2" (5.08cm) | 2" (5.08cm) | 2½" (6.35cm) | |
800,000 | 1½" (3.81cm) | 2" (5.08cm) | 2" (5.08cm) | 2" (5.08cm) | 2½" (6.35cm) | 2½" (6.35cm) | |
900,000 | 2" (5.08cm) | 2" (5.08cm) | 2" (5.08cm) | 2½" (6.35cm) | 2½" (6.35cm) | 2½" (6.35cm) | |
1,000,000 | 2" (5.08cm) | 2" (5.08cm) | 2" (5.08cm) | 2½" (6.35cm) | 2½" (6.35cm) | 2½" (6.35cm) | |
1,100,000 | 2" (5.08cm) | 2" (5.08cm) | 2½" (6.35cm) | 2½" (6.35cm) | 2½" (6.35cm) | 2½" (6.35cm) | |
1,200,000 | 2" (5.08cm) | 2" (5.08cm) | 2½" (6.35cm) | 2½" (6.35cm) | 2½" (6.35cm) | 2½" (6.35cm) | |
1,300,000 | 2" (5.08cm) | 2½" (6.35cm) | 2½" (6.35cm) | 2½" (6.35cm) | 2½" (6.35cm) | 3" (7.62cm) | |
1,400,000 | 2" (5.08cm) | 2½" (6.35cm) | 2½" (6.35cm) | 2½" (6.35cm) | 3" (7.62cm) | 3" (7.62cm) | |
1,500,000 | 2" (5.08cm) | 2½" (6.35cm) | 2½" (6.35cm) | 2½" (6.35cm) | 3" (7.62cm) | 3" (7.62cm) | |
1,600,000 | 2" (5.08cm) | 2½" (6.35cm) | 2½" (6.35cm) | 3" (7.62cm) | 3" (7.62cm) | 3" (7.62cm) | |
1,700,000 | 2" (5.08cm) | 2½" (6.35cm) | 2½" (6.35cm) | 3" (7.62cm) | 3" (7.62cm) | 3" (7.62cm) | |
1,800,000 | 2½" (6.35cm) | 2½" (6.35cm) | 3" (7.62cm) | 3" (7.62cm) | 3" (7.62cm) | 3" (7.62cm) | |
1,900,000 | 2½" (6.35cm) | 2½" (6.35cm) | 3" (7.62cm) | 3" (7.62cm) | 3" (7.62cm) | 3" (7.62cm) | |
2,000,000 | 2½" (6.35cm) | 2½" (6.35cm) | 3" (7.62cm) | 3" (7.62cm) | 3" (7.62cm) | 3½" (8.89cm) | |
2,200,000 | 2½" (6.35cm) | 3" (7.62cm) | 3" (7.62cm) | 3" (7.62cm) | 3½" (8.89cm) | 3½" (8.89cm) | |
2,400,000 | 2½" (6.35cm) | 3" (7.62cm) | 3" (7.62cm) | 3" (7.62cm) | 3½" (8.89cm) | 3½" (8.89cm) | |
2,600,000 | 2½" (6.35cm) | 3" (7.62cm) | 3" (7.62cm) | 3½" (8.89cm) | 3½" (8.89cm) | 3½" (8.89cm) | |
2,800,000 | 2½" (6.35cm) | 3" (7.62cm) | 3" (7.62cm) | 3½" (8.89cm) | 3½" (8.89cm) | 3½" (8.89cm) | |
3,000,000 | 2½" (6.35cm) | 3" (7.62cm) | 3½" (8.89cm) | 3½" (8.89cm) | 3½" (8.89cm) | 4" (10.16cm) | |
|
|
|
|
|
|
|
FOR L. P. GAS, CORRECT THE TOTAL BTU/HR. BY MULTIPLYING IT BY 0.6. THE ANSWER IS THE EQUIVALENT BTU ON THE ABOVE CHART.
IMPORTANT: The installation must conform with local codes or, in the absence of local codes:
•with the latest edition of the “National Fuel Gas Code”, ANSI Z223.1 in the U.S.A.,
•with
•and Australian Gas Association / Australian LP Gas Association requirements in Australia.
Table 2
M414545 | © Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT | 27 |