ELECTRICAL REQUIREMENTS

For 31.5" wide Tumblers

NOTE: Minimum wire sizes are obtained from Canadian Electrical Code and are intended for use as a guideline only. Electrical connections should be made only by a qualified electrical contractor in accordance with all applicable local and national requirements.

NOTE: DO NOT use aluminum wire.

Heat Source

Serial Plate Voltage

Terminal Block

Rated

Breaker

Breaker

Recommended

Connections Required

Current

Rating

Poles

Wire Size

 

 

 

 

 

 

 

 

 

Steam CSL

120V/60Hz/1ph

L1, Neutral and ground

*

20 Amps

1

12 AWG

 

 

 

 

 

 

 

Gas & CSH

120V/60Hz/1ph

L1, Neutral and ground

*

15 Amps

1

14 AWG

 

 

 

 

 

 

 

Gas & Steam

208 or 240V/60Hz/1ph

L1, L2 and ground

*

15 Amps

2

14 AWG

 

 

 

 

 

 

 

Gas & Steam

230-240V/50Hz/1ph

L1, Neutral and ground

*

15 Amps

1

14 AWG

 

 

 

 

 

 

 

Gas & Steam

208 or 240V/60Hz/3ph

L1, L2, L3, and ground

*

15 Amps

3

14 AWG

 

 

 

 

 

 

 

Gas & Steam

380 or 415V/50Hz/3ph

L1, L2, L3, and ground

*

15 Amps

3

14 AWG

 

 

 

 

 

 

 

Gas & Steam

460-480V/60Hz/3ph

L1, L2, L3, and ground

*

15 Amps

3

14 AWG

 

 

 

 

 

 

 

Electric

208V/60Hz/1ph

L1, L2, and ground

104 Amps

125 Amps

2

0 AWG

 

 

 

 

 

 

 

Electric

240V/60Hz/1ph

L1, L2, and ground

92 Amps

100 Amps

2

2 AWG

 

 

 

 

 

 

 

Electric

240V/50Hz/1ph

L1, Neutral and ground

90 Amps

100 Amps

1

2 AWG

 

 

 

 

 

 

 

Electric

208V/60Hz/3ph

L1, L2, L3, and ground

62 Amps

70 Amps

3

4 AWG

 

 

 

 

 

 

 

Electric

240V/60Hz/3ph

L1, L2, L3, and ground

55 Amps

60 Amps

3

4 AWG

 

 

 

 

 

 

 

Electric

240V/50Hz/3ph

L1, L2, L3, and ground

53 Amps

60 Amps

3

4 AWG

 

 

 

 

 

 

 

Electric

380V/50Hz/3ph

L1, L2, L3, and ground

33 Amps

40 Amps

3

8 AWG

 

 

 

 

 

 

 

Electric

415V/60Hz/3ph

L1, L2, L3, and ground

30 Amps

35 Amps

3

8 AWG

 

 

 

 

 

 

 

Electric

480V/60Hz/3ph

L1, L2, L3, and ground

28 Amps

35 Amps

3

8 AWG

 

 

 

 

 

 

 

* Current Ratings vary slightly depending on model, see nameplate.

Table 7

M414545

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

35