12 | Chapter 2 Installation |
Chapter 2 Installation
2.1Installation Preparation
2.1.1Environmental Conditions
Make sure the following environmental conditions are satisfied when selecting the installation site:
Table 2-1 Environmental conditions in power room
Environmental conditions | Recommended range |
| |
Ambient temperature | 400mm depth, it should demount the front door of cabinet to |
| ensure the normal operation of the system.) |
|
|
Humidity | ≤90%RH, |
Dust | ≤1mg/m3 |
|
|
Sunlight | No direct sunlight |
Corrosives | No pollutants, such as salt, acid, and smoke, etc. |
Shake | ≤1.5m/s2 |
|
|
Insects, pests, and termites | None |
Mildew | None |
Moisture | Water proof |
|
|
Fire protection | No flammable on the top/bottom of the cabient. |
The DC Power system will be damaged if dust or sand accumulates in it. The following measures are recommended for dusty environment:
1.The system should be installed in an airtight and
2.The air filter should be cleaned periodically.
3.The product should be installed on a cement ground.
2.1.2Power Supply
AC power supply for communication uses AC mains as its main power source. Backup batteries and generator should be configured according to the actual power supply situation. The AC power supply system composed of AC mains and generator should adopt centralized power supply mode to supply power, while low
ACTURA Flex 48330 Power System User Manual