Emerson 48330 Connection Of Load Cables, Configuration number of load MCBs and battery MCBs

Models: 48330

1 96
Download 96 pages 18.86 Kb
Page 30
Image 30

20

Chapter 2 Installation

2.3.2Connection Of Load Cables

Loads are connected to the MCB with suitable capacity to avoid their failure to function in the case of overload. The capacity of the MCBs is recommended to be about 1.5 times of the peak value of the load capacity. The load circuit breakers are shown in Figure 1-7. The circuit breakers can be ABB or CBI circuit breakers.

We take the CBI circuit breakers of 13mm for example to illustrate the load cable connection, as shown in the Figure 2-10.

connected with

 

 

connected with

 

 

 

 

high-priority load

low-priority load

 

 

 

 

busbar

busbar

 

 

 

 

 

Low-priority

 

 

 

load busbar

 

 

 

Battery –48V busbar

High-priority load busbar

Figure 2-10 Connection of load cables

Explanation: the load MCBs and battery MCBs can be configured flexible according to the actual requirements. Their setting range is shown in the following table.

Table 2-3 Configuration number of load MCBs and battery MCBs

Busbar type

Max. load number

 

Note

 

Battery -48V busbar

0~5

 

Total number of the load should not

 

 

 

 

exceed 20 with 18mm-width MCB or

 

High-priority load busbar

0~19

 

 

 

 

 

not exceed 28 with 13mm-width MCB.

 

Low-priority load busbar

0~28

 

 

 

 

 

 

 

Cable connection to MCB: strip the power cable end, crimp-connect the copper core to an H terminal, See Figure 2-4 for the cable mounted with a H terminal. After attaching the H terminal to the cable, insert the cable into the wiring hole of the MCB, then tighten the screw to fix the copper core, as shown in Figure 2-11:

Cabl e

Hterminal

Figure 2-11 Cable connection to MCB

ACTURA Flex 48330 Power System User Manual

Page 30
Image 30
Emerson 48330 Connection Of Load Cables, Configuration number of load MCBs and battery MCBs, Busbar type Max. load number