Chapter 5 Operating SCU | 49 |
Table 5-6 Logic matrix used for configuring 8 dry contacts
| Setting | 0,1 | Alarm SN | Logic Alarm SN | Logic | Alarm SN | |
| Column(B) | 0 | 1 | 2 | 3 | 4 | 5 |
| Row(A) |
|
|
|
|
|
|
Dry Contact 0 | 0 |
|
|
|
|
|
|
Dry Contact 1 | 1 |
|
|
|
|
|
|
Dry Contact 2 | 2 |
|
|
|
|
|
|
Dry Contact 3 | 3 |
|
|
|
|
|
|
Dry Contact 4 | 4 |
|
|
|
|
|
|
Dry Contact 5 | 5 |
|
|
|
|
|
|
Dry Contact 6 | 6 |
|
|
|
|
|
|
Dry Contact 7 | 7 |
|
|
|
|
|
|
The format of PLC setting is AlarmPLC[A][B]=C.
Where, “A” is the row No., and “B” is the column No., and “C” is the value of the matrix element. An example is shown in the following table:
Table 5-7 Example of PLC setting
PLC byte | Byte description | Function |
AlarmPLC[3][0]=1 | Elemant value of Row 3 and Column 0 is 1. | Use Dry Contact 3 |
|
|
|
AlarmPLC[3][1]=1 | Elemant value of Row 3 and Column 1 is 1. | Alarm SN of Fuse 1 Blow up |
|
|
|
AlarmPLC[3][2]=3 | Elemant value of Row 3 and Column 2 is 3. | AND Logic |
|
|
|
AlarmPLC[3][3]=2 | Elemant value of Row 3 and Column 3 is 2. | Alarm SN of Fuse 2 Blow up |
|
|
|
AlarmPLC[3][4]=3 | Elemant value of Row 3 and Column 4 is 3. | OR Logic |
|
|
|
AlarmPLC[3][5]=43 | Elemant value of Row 3 and Column 5 is 43. | Alarm SN of LLVD |
|
|
|
For the above PLC setting: When alarms of “Fuse 1 Blow up” and “Fuse 2 Blow up” occur at the same time, or LLVD occurs, dry contact 3 will output the alarm signal.
Relationship between PLC SN and Alarm:
|
|
|
|
| Table |
|
|
|
|
|
|
| PLC |
| Alarm |
| Remark |
| SN |
| description |
| |
|
|
|
| ||
| 0 |
| Alarm Block |
| Disabled for China Market, Enabled for rest of world |
|
|
|
|
|
|
| 1 |
| Load 1 Failure |
|
|
|
|
|
|
|
|
| 2 |
| Load 2 Failure |
|
|
|
|
|
|
|
|
| 3 |
| Load 3 Failure |
|
|
|
|
|
|
|
|
| 4 |
| Load 4 Failure |
|
|
|
|
|
|
|
|
| 5 |
| Load 5 Failure |
|
|
|
|
|
|
|
|