Appendix 1 System Technical Parameters 77
ACTURA Flex 48330 Power System User Manu al
Appendix 1 System Technical Parameters

Parameter category Note

AC input over-voltage
alarm point Default: 280 ! 5Vac, cofigurable through monitoring module
AC input over-voltage
recovery point
Default: 270 ! 5Vac, 10Vac lower than the AC input
over-voltage alarm point
AC input under-voltage
alarm point Default: 180 ! 5Vac, configurable through monitoring module
AC input alarm and
protection
AC input under-voltage
recovery point
Default: 190 ! 5Vac, 10Vac higher than the AC input
under-voltage alarm point
DC output over-voltage
protection point Default: 59.0 ! 0.2Vdc
DC output over-voltage
alarm point
Default: 58.5 ! 0.2Vdc, configurable through monitoring
module
DC output over-voltage
recovery point
Default: 58 ! 0.2Vdc, 0.5Vdc lower than the over-voltage
alarm point
DC output under-voltage
alarm point
Default: 45.0 ! 0.2Vdc, configurable through monitoring
module
DC output under-voltage
recovery point
Default: 45.5 ! 0.2Vdc, 0.5Vdc higher than the under-voltage
alarm point
LLVD Default: 44 ! 0.2Vdc, configurable through monitoring module
BLVD Default: 43.2 ! 0.2Vdc, configurable through monitoring
module
Output delay Output voltage can rise slowly upon rectifier start up. The rise
time is configurable
DC output alarm and
protection
Fan speed adjustable Rectifier fan speed can be set to half or full speed.
CS
RS EN300386 2001, Class A
Immunity to EFT EN61000-4-4, Level 3
Immunity to ESD Air discharge: 8kV. Contact discharge: 4kV. EN61000-4-2
EMC
Immunity to Surges EN61000-4-5, Level 4
Lightning protection
features At AC side
The AC input side can withstand 10/700μs simulated
lightning voltage 5kV for !5 times, or 8/20μs simulated
lightning surge current 20kA for !5 times, or 8/20μs
simulated lightning surge current 40kA once. The test interval
is not smaller than 1 minute.
Acoustic noise 55dB (A)
Others
Insulation resistance
At temperature of 15°C ~ 35°C and relative humidity not
higher than 90%RH, apply a test voltage of 500Vdc. The
insulation resistances between AC circuit and earth, between
DC circuit and earth, or between AC and DC circuits are no
less than 10MΩ