Chapter 5 Operating SCU | 57 |
LLVD Enable: Y
BLVD Enable: Y
LVD Mode:
Voltage
LVD Vlotage
LLVD: 44.0
BLVD: 43.2
LVD Time
LLVD: 300min
BLVD: 600min
Use “ ” or “ ” to select one page or one of the parameters, and “ ” or “ ” to select the parameter value. Press “ENT” to confirm and save.
Note
Generally you do not need to set the LVD parameters’ value. The defaults will do.
3.The value description of the LVD parameters is listed below. Table
| Parameter |
| Range |
| Default |
| Value description |
| LLVD Enable |
| Y, N |
| Y |
| Select “Y” to enable LLVD function |
|
|
|
|
|
| ||
| BLVD Enable |
|
|
| Select “Y” to disable the BLVD function | ||
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| LLVD Mode |
| Time, |
| Voltage |
| Select “Voltage”, when the monitoring module detects that the battery |
|
| voltage |
|
| voltage is lower than the prestet “LLVD Volt”, the load will be | ||
|
|
|
|
|
| ||
|
|
|
|
|
|
| disconnected, and so is the battery when the battery voltage is lower |
| LLVD Volt |
| 40V ~ 60V |
| 44.0V |
| |
|
|
|
|
|
| than the preset ‘BLVD Volt”. | |
| BLVD Volt |
|
| 43.2V |
| ||
|
|
|
|
| |||
|
|
|
|
|
| Select “Time”, when the discharge time reaches the preset “LLVD Time”, | |
| LLVD Time | 3 ~ 1,000 | 300min |
| |||
|
|
|
|
| the monitoring module will disconnect the load; when the discharge time | ||
|
|
|
|
| |||
| BLVD Time |
| min |
| 600min |
| |
|
|
|
| reaches the preset “BLVD Time”, it will disconnect the battery | |||
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
5.7.4Charging Management Parameters
1.There are 6 related pages, as shown below:
Float: 53.5
Boost: 56.4
Limit: 0.100C10
Over: 0.300c10
ACTURA Flex 48330 Power System User Manual