Chapter 5 Operating SCU

57

LLVD Enable: Y

BLVD Enable: Y

LVD Mode:

Voltage

LVD Vlotage

LLVD: 44.0

BLVD: 43.2

LVD Time

LLVD: 300min

BLVD: 600min

Use “ ” or “ ” to select one page or one of the parameters, and “ ” or “ ” to select the parameter value. Press “ENT” to confirm and save.

Note

Generally you do not need to set the LVD parameters’ value. The defaults will do.

3.The value description of the LVD parameters is listed below. Table 5-11 Value description of the LVD parameters

 

Parameter

 

Range

 

Default

 

Value description

 

LLVD Enable

 

Y, N

 

Y

 

Select “Y” to enable LLVD function

 

 

 

 

 

 

 

BLVD Enable

 

 

 

Select “Y” to disable the BLVD function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LLVD Mode

 

Time,

 

Voltage

 

Select “Voltage”, when the monitoring module detects that the battery

 

 

voltage

 

 

voltage is lower than the prestet “LLVD Volt”, the load will be

 

 

 

 

 

 

 

 

 

 

 

 

 

disconnected, and so is the battery when the battery voltage is lower

 

LLVD Volt

 

40V ~ 60V

 

44.0V

 

 

 

 

 

 

 

than the preset ‘BLVD Volt”.

 

BLVD Volt

 

 

43.2V

 

 

 

 

 

 

 

 

 

 

 

 

Select “Time”, when the discharge time reaches the preset “LLVD Time”,

 

LLVD Time

3 ~ 1,000

300min

 

 

 

 

 

 

the monitoring module will disconnect the load; when the discharge time

 

 

 

 

 

 

BLVD Time

 

min

 

600min

 

 

 

 

 

reaches the preset “BLVD Time”, it will disconnect the battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.7.4Charging Management Parameters

1.There are 6 related pages, as shown below:

Float: 53.5

Boost: 56.4

Limit: 0.100C10

Over: 0.300c10

ACTURA Flex 48330 Power System User Manual

Page 67
Image 67
Emerson 48330 user manual Charging Management Parameters, There are 6 related pages, as shown below