Chapter 5 Operating SCU

5.7.8DC Setting

1.There are three related pages, as shown below:

DC Volt Alarm

Over: 58.5V

Low: 45.0V

Under: 45.0V

Amb. Temp Alarm

High: 25°C

Low: 0°C

Load Shunt

None

Shunt Coeff:

None

Use “ ” or “ ” to select one page or one of the parameters, and “ ” or “ ” to select the parameter value. Press “ENT” to confirm and save.

2. The value description of the parameters is listed below: Table 5-16 Value description of DC settings

 

Parameter

 

Range

 

Default

 

Value description

 

 

Over

 

 

 

 

 

The “DC Over Voltage” alarm will be raised when

 

 

 

 

 

58.5V

 

the system DC output voltage is higher than the

 

 

(over-voltage)

 

 

 

 

 

 

 

 

 

 

 

value of “Over”

The values of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

these three

 

Low

 

 

 

 

 

The DC low voltage alarm will be raised when the

 

 

40V ~ 60V

 

45.0V

 

system DC output voltage is lower than the value

parameters should

 

(low-voltage)

 

 

 

 

 

 

 

 

 

of “Low”

be: Over > Low >

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Under

 

Under

 

 

 

 

 

The DC under voltage alarm will be raised when

 

 

 

 

45.0V

 

the system DC output voltage is lower than the

 

 

(under-voltage)

 

 

 

 

 

 

 

 

 

 

 

value of “Under”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High (high

 

10°C ~

 

 

 

The high temperature alarm will be raised when

The value of

 

 

 

40°C

 

the detected ambient temperature is higher than

 

temperature)

 

100°C

 

 

parameter “High”

 

 

 

 

 

the value of “High”

 

 

 

 

 

 

 

must be higher

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The low temperature alarm will be raised when

 

Low (low

 

-40°C ~

 

 

 

than that of

 

 

 

-5°C

 

the detected ambient temperature is lower than

 

temperature)

 

10°C

 

 

parameter “Low”

 

 

 

 

 

the value of “Low”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Load shunt

 

Y, None

 

None

 

Set according to the system actual situation

 

 

Shunt Coeff

 

Dependent

on system

 

In the system with a load shunt, this parameter can be set only when

 

 

type

 

 

 

the parameter “Shunt” (as a system type) is set to “Set”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACTURA Flex 48330 Power System User Manual

Page 74