64 | Chapter 5 Operating SCU |
5.7.8DC Setting
1.There are three related pages, as shown below:
DC Volt Alarm
Over: 58.5V
Low: 45.0V
Under: 45.0V
Amb. Temp Alarm
High: 25°C
Low: 0°C
Load Shunt
None
Shunt Coeff:
None
Use “ ” or “ ” to select one page or one of the parameters, and “ ” or “ ” to select the parameter value. Press “ENT” to confirm and save.
2. The value description of the parameters is listed below: Table
| Parameter |
| Range |
| Default |
| Value description |
|
| Over |
|
|
|
|
| The “DC Over Voltage” alarm will be raised when |
|
|
|
|
| 58.5V |
| the system DC output voltage is higher than the |
| |
|
|
|
|
|
| |||
|
|
|
|
|
| value of “Over” | The values of | |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| these three |
| Low |
|
|
|
|
| The DC low voltage alarm will be raised when the | |
|
| 40V ~ 60V |
| 45.0V |
| system DC output voltage is lower than the value | parameters should | |
|
|
|
| |||||
|
|
|
|
|
| of “Low” | be: Over > Low > | |
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| Under |
| Under |
|
|
|
|
| The DC under voltage alarm will be raised when | |
|
|
|
| 45.0V |
| the system DC output voltage is lower than the |
| |
|
|
|
|
|
| |||
|
|
|
|
|
| value of “Under” |
| |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| High (high |
| 10°C ~ |
|
|
| The high temperature alarm will be raised when | The value of |
|
|
| 40°C |
| the detected ambient temperature is higher than | |||
| temperature) |
| 100°C |
|
| parameter “High” | ||
|
|
|
|
| the value of “High” | |||
|
|
|
|
|
|
| must be higher | |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| The low temperature alarm will be raised when | |
| Low (low |
|
|
|
| than that of | ||
|
|
|
| the detected ambient temperature is lower than | ||||
| temperature) |
| 10°C |
|
| parameter “Low” | ||
|
|
|
|
| the value of “Low” | |||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| Load shunt |
| Y, None |
| None |
| Set according to the system actual situation |
|
| Shunt Coeff |
| Dependent | on system |
| In the system with a load shunt, this parameter can be set only when | ||
|
| type |
|
|
| the parameter “Shunt” (as a system type) is set to “Set”. | ||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
ACTURA Flex 48330 Power System User Manual