Emerson 48330 user manual AC Settings, Configuration interface is shown below

Models: 48330

1 96
Download 96 pages 18.86 Kb
Page 73
Image 73

 

 

 

 

 

 

Chapter 5 Operating SCU

63

 

 

 

 

 

 

 

 

 

 

Parameter

 

Range

Default

Value description

 

 

 

When Temp 1

 

 

10 C ~

 

When the detected battery temperature is

 

 

 

or Temp 2 is

Over

 

50°C

higher than the “Over”, the monitoring

The “High”

 

 

100 C

 

set to “Battery

 

 

 

module will raise an alarm

must not be

 

 

 

 

 

 

Temp”

 

 

 

 

 

higher than

 

 

 

10°C ~

 

When the detected battery temperature is

 

 

High

 

50°C

higher than the “High”, the monitoring

the “Over”

 

 

 

100°C

 

 

 

 

 

module will raise an alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

 

-40°C ~

0°C

The monitoring module will raise an alarm when the

 

 

 

 

10°C

detected battery temperature is lower than the “Low”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.7.7AC Settings

1.The configuration interface is shown below:

OverVolt: 240V

LowVolt: 210V

UnderVolt: 200V

AC Input: None

Use “ ” or “ ” to select one page or one of the parameters, and “ ” or “ ” to select the parameter value. Press “ENT” to confirm and save.

2.The value description of the parameters is listed below: Table 5-15 Value description of AC settings

 

Parameter

 

Range

 

Default

 

Value description

 

 

OverVolt

 

50V ~

 

280V

 

The monitoring module will raise an alarm when

The “OverVolt” must be

 

 

300V

 

 

the AC input voltage is higher than the “OverVolt”

higher than the “LowVolt”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To avoid alrm disorder, it

 

 

 

50V ~

 

 

 

The monitoring module will raise an alarm when

 

LowVolt

 

 

170V

 

is suggested to use the

 

 

300V

 

 

the AC input voltage is lower than the “LowVolt”.

 

 

 

 

 

 

default values

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The monitoring module will raise an alarm when

 

 

UnderVolt

 

50V ~

 

80V

 

the AC voltage of an operating route is lower than

The “UnderVolt” must be

 

 

300V

 

 

the “UnderVolt”, but there will be no alarm when

lower than the “LowVolt”.

 

 

 

 

 

 

the AC voltage of the standby route is lower than

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the “UnderVolt”

 

 

 

 

 

 

 

 

 

 

 

 

 

3-phase,

 

Dependat

 

Set this parameter according to the actual situation. In a system with an AC

 

AC Input

 

Single

 

on

 

sampling board, you can only select “Single Phase” or “3-phase”; in a system

 

 

Phase,

 

system

 

 

 

 

 

 

without an AC sampling board, you can select only “None”.

 

 

 

None

 

type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACTURA Flex 48330 Power System User Manual

Page 73
Image 73
Emerson 48330 user manual AC Settings, Configuration interface is shown below