Chapter 5 Operating SCU

59

Table 5-12 Charging management parameter value description

 

Parameter

 

Range

 

Default

 

Value description

 

Float

 

 

 

53.5V

 

In the FC state, all rectifiers output

 

 

 

 

 

 

voltage according to the set “Float”

The “Boost” must be

 

 

 

42V ~ 58V

 

 

 

 

 

 

 

 

 

 

higher than the “Float”

 

Boost

 

 

56.4V

 

In the BC state, all rectifiers output

 

 

 

 

 

 

 

 

 

 

voltage according to the set “Boost”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the monitoring module detects that the battery charging

 

Limit (current

 

 

 

 

 

current is higher than the “Limit”, it will control the current of the

 

 

0.1 ~ 0.25C10

 

0.1C10

 

rectifiers, through which it can limit the battery charging current.

 

limit)

 

 

 

 

 

 

 

 

 

C10 is the battery rated capacity, generally set to 10 ~ 20% of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rated capacity of one battery string.

 

 

 

 

 

 

 

 

 

 

Over (over current

 

 

 

 

 

When the monitoring module detects that the battery charging

 

 

0.3C10 ~ 1.0C10

 

0.300C10

 

current is higher than the “Over”, it will raise the battery charge

 

point)

 

 

 

 

 

over-current alarm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic Boost

 

Yes, No

 

Y

Select “Y”, and BC will be conducted when conditions allow

 

 

 

 

 

 

 

 

Cyclic Boost

 

 

 

 

 

Select “Y”, and the monitoring module will control the system to

 

Cyclic Boost

 

48 ~ 8760h

 

2400h

 

enter the Cyclic Boost when the FC time reaches the “Cyclic Boost

 

Interval

 

 

 

Interval”. The battery charging voltage is the preset “Boost”, and

 

 

 

 

 

 

 

 

 

 

 

 

the time is the preset “Cyclic Boost Time”

 

Cyclic Boost Time

30 ~ 2880min

 

720min

 

 

 

 

 

 

 

 

 

To Boost Current

0.50 ~ 0.80C10

 

0.06C10

 

The monitoring module will control the system enter the BC state

 

To Boost

 

 

 

 

 

when the battery capacity decreases to the value of “To Boost

 

0.1 ~ 0.95

0.80

 

Capacity”, or when the charge current reaches the “To Boost

 

Capacity

 

 

 

 

 

 

 

Current”. The charge voltage will be the “Boost”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Constant BC Curr

 

0.02 ~ 0.99C10

 

0.01C10

 

The system in the BC state will enter the FC state when the charge

 

Duration (of

 

30 ~ 1440min

 

180min

 

current decreases to the “Constant BC Curr” and after the

 

constant BC)

 

 

 

“Duration”. The battery charge voltage then will be the “Float”.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To ensure safety, the monitoring module will forcefully control the

 

Boost Limit

60 ~ 2880min

 

1080min

 

system to enter the FC state if during the BC state, the BC time

 

 

 

reaches the “Boost Limit”, or abnormalities occur (such as AC

 

 

 

 

 

 

 

failure and battery route faulty, etc.).

 

 

 

 

 

 

 

 

 

 

3. The BC/FC switchover diagram is shown below:

FC time longer than "Scheduled BC Interval"

Battery charge current bigger than "To BC Current"

Battery capacity smaller than "To BC Capacity"

FC

 

 

BC

 

Constant BC

 

Charge current

 

 

smaller than

 

time-up

 

 

Constant

"Constant BC

 

 

 

 

Curr"

 

 

BC

 

 

 

BC time longer than "BC LVD Time"

Abnormal situation

Figure 5-2 BC/FC switchover diagram

ACTURA Flex 48330 Power System User Manual