Chapter 5 Operating SCU

65

5.7.9Rect Settings

1.There are three related pages, as shown below:

Rect Over Volt:

59.0V

Default Volt:

42.0V

Walk-in Enabled

N

Walk-in Time:

8s

Fan Speed

Full Speed

HVSD Time:

300s

Use “ ” or “ ” to select one page or one of the parameters, and “ ” or “ ” to select the parameter value. Press “ENT” to confirm and save.

2. The value description of the parameters is listed below:

Table 5-17 Value description of rectifier settings

 

Parameter

 

Range

 

Default

 

Value description

 

 

 

 

 

 

 

The rectifier over voltage alarm will be

 

 

 

Rect Over Volt

56V ~ 59V

 

59V

 

raised when the rectifier output voltage is

 

The “Default Volt” must be

 

 

 

 

 

 

 

higher than the “Rect Over Volt”

 

lower than the “Rect Over Volt”

 

 

 

 

 

 

 

 

 

 

Default Volt

48V ~ 58V

 

53.5V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Walkin Enabled

 

Y, N

 

N

 

The output soft start function means the

rectifier voltage will rise from 0V

 

 

 

 

 

 

 

to the “Default Volt” after the “Walkin Time”

 

 

Walkin Time

 

8s ~ 128s

 

10s

 

 

 

 

 

 

 

 

 

 

 

 

Full Speed,

 

Half

When set to “Half Speed”, the rectifier will regulate the fan speed

 

Fan Speed

 

 

according to the temperature. When set to “Full Speed”, the fan will

 

 

Half Speed

 

speed

 

 

 

 

operate at full speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The rectifier will shut off automatically upon over-voltage, and restart after

 

 

 

 

 

 

 

a certain delay to see whether it is still over-voltage then. That delay is set

 

HVSD Time

50s ~ 300s

 

300s

 

through the parameter “HVSD Time”. If the rectifier’s output voltage is

 

 

 

 

 

 

 

normal within the delay, the rectifier is regarded normal; otherwise, the

 

 

 

 

 

 

 

rectifier will be locked out and auto-restart function will be disabled

 

 

 

 

 

 

 

 

 

 

ACTURA Flex 48330 Power System User Manual