Emerson 48330 user manual LVD Parameter Description

Models: 48330

1 96
Download 96 pages 18.86 Kb
Page 66
Image 66

56

Chapter 5 Operating SCU

3.If setting parameter “System Type” requires setting the battery shunt coefficient, the second page of the basic battery settings is as follows:

Batt Shunt1: Yes

Batt Shunt2: No Shunt Coeff: 300A / 75mV

4.The value description of the basic battery parameters is listed below: Table 5-10 Value description of the basic battery parameters

 

Parameter

 

Range

 

Defaults

 

Value description

 

 

 

 

 

 

 

In normal situation, it should be in the “Auto” mode, which enables

 

 

 

 

 

 

 

the monitoring module manage the whole power system

 

Mgmt Mode

 

 

 

 

 

automatically, including: Automatic FC/BC switchover, LLVD and

 

 

 

 

 

 

BLVC. In the manual mode, you can do operations like BC, FC,

 

(Management

 

Auto, Manual

 

Auto

 

 

 

 

 

test and battery on/off, as well as enabling automatic battery BC

 

mode)

 

 

 

 

 

 

 

 

 

 

 

time protection and capacity calculation. Upon the system DC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

under-voltage alarm, system can automatically switch to the “Auto”

 

 

 

 

 

 

 

mode, lest wrong manual operation should damage the system

 

 

 

 

 

 

 

 

 

Batt String

 

 

 

 

 

You should set this parameter according to the actual battery

 

(number of

0 ~ 4

4

 

configuration. If “Batt Shunt” is set as “Y”, there should be batteries

 

battery strings)

 

 

 

 

 

actually configured

 

 

 

 

 

 

 

 

 

Rated AH (rated

 

50 ~ 5000Ah

300Ah

 

The capacity of a single battery string. You should set this

 

capacity)

 

 

parameter according to the actual battery configuration.

 

 

 

 

 

 

 

 

 

 

 

 

 

BTT Name

1# ~ 11#

1#

 

 

 

 

 

 

 

 

 

Battery Name

10 characters

 

 

Name different battery types to identify them

 

 

 

 

 

 

 

 

 

Batt Shunt1

 

 

 

Yes

 

Select “Y” when a corresponding shunt is configured, otherwise,

 

 

 

Yes, No

 

 

 

select “N”. Battery management aims at only the batteries

 

Batt Shunt2

 

 

No

 

 

 

 

 

 

connected to the shunt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shunt Coeff

 

 

 

 

 

In the system type setting, if the parameter “Shunt” is set to “Y”,

 

(shunt

 

Dependent on system type

 

this parameter will be displayed. Otherwise this parameter will take

 

coefficient)

 

 

 

 

 

the default value, and is the same for both battery strings.

 

 

 

 

 

 

 

 

5.7.3LVD Parameter Description

1. Function description

LLVD means the monitoring module opens the LLVD contactor, so that the non-priority load will be powered off. In this way, the battery remaining capacity can sustain the priority load longer.

BLVD means the monitoring module opens the BLVD contactor. In this way, the battery will stop powering the load, preventing over-discharge.

2. There are 3 related pages, as shown below:

ACTURA Flex 48330 Power System User Manual

Page 66
Image 66
Emerson 48330 user manual LVD Parameter Description