54Chapter 5 Operating SCU
2.Use “ ” or “ ” to select the submenu “Settings” and press “ENT” to confirm. System will then prompt you to input the password.
Enter Password: 123456
3.Press " " or " digit by digit using “ setting submenu.
"to select the number of password digits. Enter the password
”or “ ”. Press “ENT” to confirm and enter the parameter
Settings
Alarms Settings
Battery Settings
AC Settings
Parameter Set
DC Settings
Rect Settings
Sys Settings
Users with different password levels have different authorities. See the following table:
Table 5-9 Password levels and authorities
| Level |
| Authority |
| User |
| Configuration of general parameters |
| Operator |
| User’s authority, plus resetting system, resetting |
|
| password and modifying system type. | |
|
|
| |
|
|
|
|
|
|
| Operator’s authority, plus modifying password of all |
| Administrator |
| levels, controling alarm sound volume, browsing system |
|
|
| parameters that can be set only through the host |
|
|
|
|
Default password
123456
654321
640275
4.There are two pages of “Settings”. Shift page by using “ ” or “ ”, and select the parameter by using “ ” or “ ”. Press “ENT” to confirm.
As shown in the above figure, the monitoring module divides the parameters to be set into 6 kinds: alarms parameter, battery parameter, AC parameter, DC parameter, rectifier parameter and system parameter.
Among which, the battery parameters are divided into 5 kinds: basic, BLVD, charging management, battery test, temperature coefficient, and they are displayed in two pages, as shown below:
ACTURA Flex 48330 Power System User Manual