Chapter 6 Routine Maintenance

After one year of operation, all the units should be within the range of 13.50±0.48V.

6.5.3Replacement

1)Replacing Criterion

Replace the battery if its capacity measured during the battery test is less than 80% of the battery rated capacity. The capacity measured during the battery test shall be evaluated at a discharge rate close to its actual use.

2) Replacement Interval

The battery is expendable, and has a certain life cycle. Considering the use condition and ambient temperature, the new battery should replace the old battery before it reaches its design life to ensure the normal and safety operation of the DC power system. For instance, in an environment where the mean temperature is 35°C, it is necessary to replace the battery every 5-year operation.