Chapter 5 Operating SCU | 35 |
5.2Operation Procedures
After the system is powered on for the first time, you should set the system type according to the actual configuration. The monitoring module will restart after the system type is changed. In that case, you should
After configuring the system parameters, you can carry out various operations directly without resetting the parameter values. As for those important parameters related to battery management, such as BLVD, you should be fully aware of their influence upon the system before you change their values.
Note
For the exact meanings of the abbreviations used in LCD displayer, see Appendix E Glossary.
1.The LCD will prompt you to select a language once the monitoring module is powered on.
英文
English
You can use “ ”, “ ”, “ ” or “ ” to select the language you want, and press “ENT” to confirm.
2. The monitoring module will prompt you to wait, and start initialization.
Waiting……..
3. The first system information page appears
53.5V 125 A System: No alarm Auto /BC
The system information is shown in many pages. You can repeatedly press “ ” to view other system information pages in a cycle.
ACTURA Flex 48330 Power System User Manual