Chapter 5 Operating SCU

4.At any system information page, press “ENT” to enter the “MAIN MENU” page, which contains 3 sub-menus: “Status”, “Maintenance” and “Settings”.

Main Menu

Status

Maintenance

Settings

You can press “ ” or “ ” repeatedly to select a sub-menu, and press “ENT” to enter the sub-menu. Press “ESC” to return to the menu of higher level.

1) Status

Including rectifier information, active alarm information and alarm history information.

2) Maintenance

The maintenance operation can be conducted only when the battery management mode is set to “Manual”. The maintenance includes battery FC, BC and test, load power off/on, battery power off/on and rectifier voltage trimming, current limit, switch control and resetting.

3) Settings

Including the setting of alarm parameter, battery parameter, AC/DC parameter, rectifier parameter and system parameter.

5.3Querying System Status

5.3.1First Page Of System Information

1.At the main menu page, press “ESC” to return to the first system information page.

2.If no operation is conducted on the monitoring module keypad for 8 minutes, the LCD will return to the first system information page and shut down the backlight to protect the screen. Pressing any key will turn on the back light.

The first system information page contains the major system operation information, including date/time, busbar voltage, total load current, system operation state (normal or alarm), battery management mode (AUTO or MANUAL) and battery state.

Among which, the battery state include FC, temperature compensation, BC, Cyclic Boost, test, short test and scheduled test. The current time are displayed in two pages shifting at the interval of 2s. One page shows year, month and date, the

ACTURA Flex 48330 Power System User Manual

Page 46
Image 46