Chapter 5

Operating SCU

45

 

 

 

 

 

 

 

 

 

Serial

Alarm

Description

Default

Default

Related parameter

 

 

related

 

 

No.

alarm level

configuration

 

 

 

 

relay

 

 

 

 

 

 

 

 

 

36

Batt4 Failure

Over-load, short circuit, manual

Critical

None

 

 

 

disconnection or alarm circuit faulty

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The charge current of battery group 1

 

 

 

 

 

37

Batt1 Over-curr

is bigger than the set value of

Observation

None

 

 

 

 

 

parameter “Over”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The charge current of battery group 2

 

 

 

 

 

38

Batt2 Over-curr

is bigger than the set value of

Observation

None

 

 

 

 

 

parameter “Over”

 

 

 

 

 

 

 

 

 

 

 

 

 

39

Rect Vac Err

All AC voltages are lower than the

Major

3

 

 

 

AC low-volt point

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

Rect Over Temp

Rectifier internal temperature higher

Observation

None

 

 

 

 

 

than 90°C

 

 

 

 

 

41

Rect Failure

Rectifier over-voltage, higher than

Critical

3

 

 

 

rectifier high threshold

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

42

Rect Protect

AC over-voltage (ƒ295V) or

Observation

3

 

 

 

under-voltage ( 80V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43

Rect Fan Fails

Fan faulty

Major

3

 

 

 

 

 

AC voltage lower than 176V, with

 

 

 

 

 

44

Rect PowerLimit

rectifier internal higher than 85°C or

Observation

3

 

 

 

 

 

temperature at inlet higher than 45°C

 

 

 

 

 

 

 

 

 

 

 

 

 

45

Rect Com Failure

Rectifier and monitoring module

Major

3

 

 

 

communication interrupted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

46

Multi Rect Fail

More than 2 rectifiers raised alarms

Critical

None

 

 

 

47

Self-detect error

Error is detected through hardware

No alarm

None

 

 

 

self-detection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

48

Manual Mode

Battery management in the manual

No alarm

None

 

 

 

state

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

49

Non-FC Status

Including auto-BC, Cyclic Boost,

No alarm

7

 

 

 

constant current test and short test

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

Batt Discharge

Battery being discharging

No alarm

None

 

 

 

 

 

In a system with load shunt, the

 

 

 

 

 

51

Curr Imbalance

detected load current plus battery

No alarm

None

Not existent in this

 

 

 

 

current differs sharply from the

 

 

power system series

 

 

 

 

rectifier output current

 

 

 

 

 

 

 

 

 

 

 

 

 

52

Batt Test Error

Battery discharge time unexpectedly

Observation

None

 

 

 

 

 

short

 

 

 

 

 

 

 

During the short test, the two

 

 

 

 

 

53

Short Test Fault

batteries discharged more than the

Observation

None

 

 

 

 

 

set value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The maintenance FC voltage

 

 

 

 

 

54

Outvolt Fault

different from the busbar voltage, or

Observation

None

 

 

 

the reported data. The difference is

 

 

 

 

 

 

 

 

 

 

 

 

more than 1V

 

 

 

 

 

 

 

 

 

 

 

 

 

55

System Maintain

The pre-set system maintenance

Observation

None

 

 

 

time is due

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

56

Alarm Block

Alarms sent to the host are blocked,

No alarm

None

 

 

 

 

 

valid in EEM-M protocol

 

 

 

 