78 Appendix 1 System Technical Parameters

 

Parameter

 

category

 

Note

 

 

Others

 

 

(Remove the SPD, monitoring module and rectifiers from the

 

 

 

 

system before the test.)

 

 

 

 

 

AC to DC circuits, AC circuit to earth: 50Hz, 3,000Vac (RMS).

 

 

 

 

DC circuit to earth: 50Hz, 1,000Vac (RMS).

 

 

 

Dielectric strength

Assistant circuit (not directly connected to the host circuit):

 

 

 

 

50Hz, 500Vac (RMS).

 

 

 

 

 

For all the three tests above, there should be no breakdown

 

 

 

 

or flashover within 1min, with leakage current not bigger than

 

 

 

 

10mA.

 

 

 

 

 

 

 

 

 

 

 

 

MTBF

250,000hr

 

 

 

 

 

Size (mm)

600 (W) % 600 (D)

600 (W) % 400

600 (W) % 400 (D)

 

 

 

% 2000 (H)

(D) % 2000 (H)

% 700 (H)

 

Mechanica

 

 

 

 

 

 

 

 

 

 

Weight

<135kg (without

<125kg (without

<60kg (without

 

 

 

 

 

 

rectifiers)

rectifiers)

rectifiers)

 

 

 

 

 

 

 

 

 

 

 

ACTURA Flex 48330 Power System User Manual