Graco 332564B important safety instructions Network Input Data Map Write/Read, None

Models: 332564B

1 104
Download 104 pages 58.79 Kb
Page 40
Image 40

Operation Using a Programmable Logic Controller (PLC)

Network Input Data Map (Write/Read)

Network

Modbus

Parameter Name

Data

Units

Range

Input ID

Register

 

Type

 

 

 

 

 

 

 

 

 

00

40156

System Mode Command

uint32

NONE

0 = No

 

 

 

 

 

1

= Power Pumps

 

 

 

 

 

2

= Remote Stop

 

 

 

 

 

3

= Recipe Change

 

 

 

 

 

4

= Mix Fill

 

 

 

 

 

5

= Mix

 

 

 

 

 

6

= Purge A

 

 

 

 

 

7

= Purge B

 

 

 

 

 

8

= Standby

 

 

 

 

 

 

01

40158

Pump Flush Sequence #/Prime

uint32

NONE

1 - 5, 1 - 34

 

 

Material #

 

 

 

 

02

40160

Flush/Prime Pump Command

uint32

NONE

0 = No OP

 

 

 

 

 

1

= Flush Pump 1

 

 

 

 

 

2

= Prime Pump 1

 

 

 

 

 

3

= Flush Pump 2

 

 

 

 

 

4

= Prime Pump 2

 

 

 

 

 

5

= Flush Pump 3

 

 

 

 

 

6

= Prime Pump 3

 

 

 

 

 

7

= Flush Pump 4

 

 

 

 

 

8

= Prime Pump 4

03

40162

Mix (Pump 1) Control Set Point

uint32

cc/min or

1 - 1600

 

 

 

 

PSI

 

 

04

40164

Pump 2 Control Set Point

uint32

cc/min or

1 - 1600

 

 

 

 

PSI

 

 

05

40166

Pump 3 Control Set Point

uint32

cc/min or

1 - 1600

 

 

 

 

PSI

 

 

06

40168

Pump 4 Control Set Point

uint32

cc/min or

1 - 1600

 

 

 

 

PSI

 

 

07

40170

Go to Recipe Number

uint32

NONE

0, 1 - 60

 

 

 

 

 

 

08

40172

Clear Active Alarm

uint32

NONE

1 = Clear Active Alarm

 

 

 

 

 

 

09

40174

Job Complete

uint32

NONE

1 = Trigger job complete

10

40176

Gun 1 Trigger

uint32

NONE

0 = Gun not triggered

 

 

 

 

 

1

= Gun triggered

11

40178

Gun 2 Trigger

uint32

NONE

0 = Gun not triggered

 

 

 

 

 

1

= Gun triggered

40

332564B

Page 40
Image 40
Graco 332564B important safety instructions Network Input Data Map Write/Read, None