Setup Mode Screens

Pump Screen 3

Pump screen 3 sets the pressure alarm limits for the pump.

When Inlet Pressure in Pump Screen 1, page 74 is set to Disabled, the inlet limit fields are grayed out and only the outlet limit fields are active. See Pressure Alarm and Deviation Limits, page 76.

Figure 39 Pump Screen 3, Pressure Monitoring Disabled

When Inlet Pressure in Pump Screen 1, page 74 is set to Monitor, all fields are active. See Pressure Alarm and Deviation Limits, page 76.

Figure 40 Pump Screen 3, Pressure Monitoring Enabled

Pressure Alarm and Deviation Limits

Inlet fields are only active if Inlet Pressure

in Pump Screen 1, page 74 is set to Monitor; they are grayed out if set to Disabled. Outlet fields are active at all times.

Alarm and Deviation ranges are 0-300 psi for low pressure systems, and 0-1500 psi for high pressure systems.

Setting to 0 will disable the alarm. The Inlet Alarm High and Outlet Alarm High cannot be disabled.

Alarms and Deviations will display when the inlet or outlet pressure drops below the low limit or exceeds the high limit.