Graco 332564B Default Settings Selected, Default Settings Not Selected

Models: 332564B

1 104
Download 104 pages 58.79 Kb
Page 75
Image 75

Pump Screen 2

Pump screen 2 sets the pressure transducer settings for the pump.

Figure 37 Pump Screen 2, Default Settings Enabled

Figure 38 Pump Screen 2, Default Settings Disabled

Setup Mode Screens

Default Settings Selected

When the “Use Default Settings” box is selected, default settings are used for the calibration values, and the fields are grayed out.

Default Settings Not Selected

When the “Use Default Settings” box is not selected, the following calibration values must be entered. Invalid values will be over-ridden and the system will automatically select the default settings.

Inlet Offset Factor: This field is only used if Inlet Pressure in Pump Screen 1, page 74 is set to Monitor; it is grayed out if set to Disabled. The valid range is -01.20 to +01.20 mV/V.

Inlet Sensitivity Factor: This field is only used if Inlet Pressure in Pump Screen 1, page 74 is set to Monitor; it is grayed out if set to Disabled. The valid range is 18.80 to 21.20 mV/V.

Outlet Offset Factor: The valid range is -01.20 to +01.20 mV/V.

Outlet Sensitivity Factor: The valid range is 18.80 to 21.20 mV/V.

332564B

75

Page 75
Image 75
Graco 332564B important safety instructions Default Settings Selected, Default Settings Not Selected