Operation Using a Programmable Logic Controller (PLC)

Alarm Clearing Sequence

NOTE: If an alarm condition is active the System Mode will either be Pump Off or Standby: Alarm. (Output Register 00 = ‘1’ or ‘14’)

Clear Active Alarm

Write ‘1’ to Input Register 08

Is there an active

 

 

 

 

 

 

NO

 

 

No action taken.

 

alarm?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is there more than 1

 

 

 

 

YES

 

 

NO

 

 

 

active alarm?

 

 

 

 

 

 

 

 

 

Clear most recent active

alarm.

Remaining alarm(s) still

active.

Clear active alarm.

NOTE: If more than 1 active alarm exists a repeated write of ‘1’ to Input Register 08 is required for each.