L2002 Inverter

3–21

DC Braking Settings

The DC braking feature can provide

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

additional stopping torque when

Running

 

 

Free run

 

 

DC braking

 

 

 

 

 

 

 

 

 

 

 

 

 

compared to a normal deceleration to a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

stop. DC braking is particularly useful

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

at low speeds when normal decelera-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

t

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tion torque is minimal. When you

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

enable DC braking, the inverter injects

 

 

 

 

A053

 

 

 

 

A055

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a DC voltage into the motor windings

during deceleration below a frequency you can specify (A052). The braking power (A054) and duration (A055) can both be set. You can optionally specify a wait time before DC braking (A053), during which the motor will free run (coast).

CAUTION: Be careful to avoid specifying a braking time that is long enough to cause motor overheating. If you use DC braking, we recommend using a motor with a built-in thermistor, and wiring it to the inverter’s thermistor input (see “Thermistor Thermal Protection” on page 4–25). Also refer to the motor manufacturer’s specifications for duty-cycle recommendations during DC braking.

 

 

 

“A” Function

Run

 

Defaults

 

 

ParametersDrive

 

 

 

 

 

 

Mode

 

 

 

 

 

 

Func.

Name /

 

–FE(F)

–FU

 

 

 

 

Description

Edit

Units

 

Configuring

 

Code

SRW Display

Lo Hi

(EU)

(USA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A051

DC braking enable

Two options; select codes:

✘ ✔

00

00

 

 

 

 

 

 

 

00 .. Disable

 

 

 

 

 

 

 

 

 

DCB Mode

OFF

 

 

 

 

 

 

 

 

 

01 .. Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A052

DC braking frequency

The frequency at which DC

✘ ✔

0.5

0.5

Hz

 

 

 

 

 

setting

 

braking begins,

 

 

 

 

 

 

 

 

 

 

 

range is from the start

 

 

 

 

 

 

 

 

 

DCB F

0000.5Hz

 

 

 

 

 

 

 

 

 

frequency (B082) to 60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A053

DC braking wait time

The delay from the end of

✘ ✔

0.0

0.0

sec.

 

 

 

 

 

 

 

controlled deceleration to start

 

 

 

 

 

 

 

 

 

DCB Wait 0000.0s

 

 

 

 

 

 

 

 

 

of DC braking (motor free runs

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

until DC braking begins),

 

 

 

 

 

 

 

 

 

 

 

range is 0.0 to 5.0 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A054

DC braking force for

Level of DC braking force,

✘ ✔

0.

0.

%

 

 

 

 

 

deceleration

settable from 0 to 100%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCB V

00000%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A055

DC braking time for

Sets the duration for DC

✘ ✔

0.0

0.0

sec.

 

 

 

 

 

deceleration

braking, range is 0.0 to 60.0

 

 

 

 

 

 

 

 

 

 

 

seconds

 

 

 

 

 

 

 

 

 

DCB T

0000.0s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A056

DC braking / edge or

Two options; select codes:

✘ ✔

01

01

 

 

 

 

 

level detection for [DB]

00 .. Edge detection

 

 

 

 

 

 

 

 

 

input

 

01 .. Level detection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCB KIND

LEVEL