L2002 Inverter

1–11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

General Specifications

 

 

 

 

 

 

 

 

 

 

Getting

 

 

 

 

 

 

 

 

Other functions

AVR function, curved accel/decel profile, upper and lower limiters,

 

 

 

 

 

 

 

 

 

16-stage speed profile, fine adjustment of start frequency, carrier

 

 

 

 

 

 

frequency change (2 to 14 kHz) *10, frequency jump, gain and bias

 

 

 

 

 

 

setting, process jogging, electronic thermal level adjustment, retry

 

 

Started

 

 

 

function, trip history monitor, 2nd setting selection, fan ON/OFF

 

 

 

 

 

 

 

 

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

Protective function

Over-current, over-voltage, under-voltage, overload, extreme high/

 

 

 

 

 

 

low temperature, CPU error, memory error, ground fault detection at

 

 

 

 

 

 

startup, internal communication error, electronic thermal

 

 

 

 

 

 

 

 

 

 

Operat-

Temperature

Operating (ambient): -10 to 40°C (*10) / Storage: -25 to 60°C (*11)

 

 

 

 

ing

 

 

 

 

 

 

 

Humidity

20 to 90% humidity (non-condensing)

 

 

 

 

Environ

 

 

 

ment

Vibration *12

5.9 m/s2 (0.6G), 10 to 55 Hz

 

 

 

 

 

Location

Altitude 1,000 m or less, indoors (no corrosive gasses or dust)

 

 

 

 

 

 

 

 

 

 

Coating color

Blue (DIC 14 Version No. 436)

 

 

 

 

 

 

 

 

 

Options

 

Remote operator unit, copy unit, cables for the units, braking unit,

 

 

 

 

 

 

braking resistor, AC reactor, DC reactor, noise filter, DIN rail

 

 

 

 

 

mounting

 

 

 

 

 

 

 

 

 

 

Signal RatingsDetailed ratings are in “Control Logic Signal Specifications” on page 4–6.
Signal / ContactRatings

 

 

 

 

Built-in power for inputs

24VDC, 30 mA maximum

 

 

Discrete logic inputs

27VDC maximum

 

 

Discrete logic outputs

50mA maximum ON state current, 27 VDC maximum OFF state voltage

 

 

Analog output

0 to 10VDC, 1 mA

 

 

Analog input, current

4 to 19.6 mA range, 20 mA nominal

 

 

Analog input, voltage

0 to 9.6 VDC range, 10VDC nominal, input impedance 10 kΩ

 

 

+10V analog reference

10VDC nominal, 10 mA maximum

 

 

Alarm relay contacts

250 VAC, 2.5A (R load) max., 0.2A (I load, P.F.=0.4) max.

 

100 VAC, 10mA min.

 

30 VDC, 3.0A (R load) max., 0.7A (I load, P.F.=0.4) max.

 

5 VDC, 100mA min.