L2002 Inverter

 

B–29

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Holding Registers for “A” Group Standard Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Network Data

 

 

 

Func.

 

 

 

 

 

 

 

 

 

 

Name

R/W

Description

Register

 

 

 

 

 

Code

Range

Res.

 

 

 

 

 

 

 

 

 

 

 

 

 

hex

dec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A056

DC braking / edge or

R/W

Two options; select codes:

1056h

04182

0, 1

 

 

 

 

level detection for [DB]

 

00... Edge detection

 

 

 

 

 

 

 

 

input

 

01... Level detection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A061

Frequency upper limit

R/W

Sets a limit on output

105Ah

04186

(A062 x

0.1 Hz

 

 

 

 

 

setting

 

frequency less than the

 

 

10) to

 

 

 

 

 

 

maximum frequency (A004).

 

 

(A004 x

 

 

 

A261

Frequency upper limit

R/W

1517h

05399

 

 

 

Range is from frequency

10),

 

 

 

BAppendix

 

setting, 2nd motor

 

lower limit (A062) to

 

 

0=disable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

maximum frequency (A004).

 

 

>1=enabl

 

 

 

 

 

 

0.0.. setting is disabled

 

 

e

 

 

 

 

 

 

>0.1setting is enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A062

Frequency lower limit

R/W

Sets a limit on output

105Bh

04187

(B082 x

0.1 Hz

 

 

 

setting

 

frequency greater than zero.

 

 

10) to

 

 

 

 

 

 

Range is start frequency

 

 

(A061 x

 

 

 

A262

Frequency lower limit

R/W

1518h

05400

 

 

 

(B082) to frequency upper

10),

 

 

 

 

 

setting, 2nd motor

 

 

 

 

 

 

 

 

limit (A061).

 

 

0=disable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0.. setting is disabled

 

 

>1=enabl

 

 

 

 

 

 

>0.1setting is enabled

 

 

e

 

 

 

 

 

 

 

 

 

 

 

 

 

A063,

Jump (center) frequency

R/W

Up to 3 output frequencies

105Dh

04189

0 to 4000

0.1 Hz

 

 

A065,

setting

 

can be defined for the output

1060h

04192

 

 

 

 

 

A067

 

 

to jump past to avoid motor

1063h

04195

 

 

 

 

 

 

 

 

resonances (center frequency)

 

 

 

 

 

 

 

 

 

 

Range is 0.0 to 400.0 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A064,

Jump (hysteresis)

R/W

Defines the distance from the

105Eh

04190

0 to 100

0.1 Hz

 

 

A066,

frequency width setting

 

center frequency at which the

1061h

04193

 

 

 

 

 

A068

 

 

jump around occurs

1064h

04196

 

 

 

 

 

 

 

 

Range is 0.0 to 10.0 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A071

PID Enable

R/W

Enables PID function,

1068h

04200

0, 1

 

 

 

 

 

 

two option codes:

 

 

 

 

 

 

 

 

 

 

00... PID Disable

 

 

 

 

 

 

 

 

 

 

01... PID Enable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A072

PID proportional gain

R/W

Proportional gain has a range

1069h

04201

2 to 50

0.1

 

 

 

 

 

of 0.2 to 5.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A073

PID integral time

R/W

Integral time constant has a

106Ah

04202

0 to 1500

0.1 sec

 

 

 

constant

 

range of 0.0 to 150 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A074

PID derivative time

R/W

Derivative time constant has a

106Bh

04203

0 to 1000

0.1 sec

 

 

 

constant

 

range of 0.0 to 100 seconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A075

PV scale conversion

R/W

Process Variable (PV) scale

106Ch

04204

1 to 9999

0.01

 

 

 

 

 

factor (multiplier), range of

 

 

 

 

 

 

 

 

 

 

0.01 to 99.99