4–15

L2002 Inverter

Jogging Command

The Jog input [JG] is used to command the motor to rotate slowly in small increments for manual operation. The speed is limited to

10 Hz. The frequency for the jogging operation is set by parameter A038. Jogging does not use an acceleration ramp, so we recommend setting the jogging frequency A038 to 5 Hz or less to prevent tripping.

When the terminal [JG] is turned ON and the Run command is issued, the inverter outputs the programmed jog frequency to the motor. To enable the Run key on the digital operator for jog input, set the value 01(terminal mode) in A002 (Run command source).

[JG] 1 0

[FW], 1 [RV] 0

Jog

speed

A038

A039 Jog decel type

t

The type of deceleration used to end a motor jog operation is selectable by programming function A039. The options are:

00 Free-run stop (coasting)01 Deceleration (normal level) and stop02 Use DC braking and stop

Option

Terminal

Function Name

Input

 

 

Description

Code

Symbol

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

JG

Jogging

ON

Inverter is in Run Mode, output to motor runs at

 

 

 

 

jog parameter frequency

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Inverter is in Stop Mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for inputs:

C001, C002, C003, C004,

Example (requires input configuration—see

C005

 

 

 

 

page 3–47):

 

 

 

 

Required settings:

A002= 01, A038 > B082,

 

 

 

 

 

 

 

 

 

A038 > 0, A039

 

 

 

 

 

JG

 

 

 

 

 

 

 

 

 

 

 

 

L

5

4

3

2

1

PCS

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No jogging operation is performed when the set

value of jogging frequency A038 is smaller than the start frequency B082, or the value is 0 Hz.

Be sure to stop the motor when switching the function [JG] ON or OFF.

See I/O specs on page 4–6.