6–3

L2002 Inverter

Troubleshooting TipsThe table below lists typical symptoms and the corresponding solution(s).
Symptom/condition

 

Probable CauseSolution

 

 

 

 

 

 

 

 

 

 

 

Is the frequency command source

Make sure the parameter

 

 

 

A001 parameter setting correct?

setting A001 is correct.

 

 

Is the Run command source A002

Make sure the parameter

 

 

 

parameter setting correct?

setting A002 is correct.

 

 

 

 

 

 

Is power being supplied to termi-

Check terminals [L1], [L2],

 

 

 

nals [L1], [L2], and [L3/N]? If so,

and [L3/N], then [U/T1],

 

 

 

the POWER lamp should be ON.

[V/T2], and [W/T3].

 

 

 

 

Turn ON the power supply

 

 

 

 

or check fuses.

 

 

 

 

 

 

 

Is there an error code E X X

Press the Func. key and

 

The inverter

 

displayed?

determine the error type.

 

 

 

Eliminate the error cause,

 

outputs [U], [V],

 

 

then clear the error (Reset).

 

[W] are not

 

 

 

 

Are the signals to the intelligent

Verify the terminal functions

 

supplying

 

 

input terminals correct?

for C001 – C005 are correct.

 

voltage.

 

 

Is the Run Command active?

Turn ON Run Command

The motor

 

 

Is the [FW] terminal (or [RV])

enable.

will not run.

 

 

 

connected to [PCS] (via switch,

Supply 24V to [FW] or [RV]

 

 

 

 

 

 

etc.)

terminal, if configured.

 

 

 

 

 

 

Has the frequency setting for F001

Set the parameter for F001

 

 

 

been set greater than zero?

to a safe, non-zero value.

 

 

Are the control circuit terminals

If the potentiometer is the

 

 

 

[H], [O], and [L] connected to the

frequency setting source,

 

 

 

potentiometer?

verify voltage at [O] > 0V.

 

 

 

 

 

 

Is the RS (reset) function or FRS

Turn OFF the command(s).

 

 

 

(free-run stop) function ON?

 

 

 

 

 

 

 

Inverter outputs

Is the motor load too heavy?

Reduce load, and test the

 

[U], [V], [W]

 

 

motor independently.

 

are supplying

 

 

 

 

voltage.

 

 

 

 

 

 

 

 

 

The optional

Are the operational settings

Check the operator type

 

remote operator

 

between the remote operator and

setting.

 

is used (SRW).

 

the inverter unit correct?

 

 

 

 

 

 

 

Are the connections of output

Make connections according

 

 

 

terminals [U/T1], [V/T2], and

to the phase sequence of the

 

 

 

[W/T3] correct?

motor. In general:

 

 

Is the phase sequence of the motor

FWD = U-V-W, and

The direction of the motor is

 

forward or reverse with respect to

REV=U-W-V.

 

 

 

[U/T1], [V/T2], and [W/T3]?

 

reversed.

 

 

 

 

 

 

 

Are the control terminals [FW] and

Use terminal [FW] for

 

 

 

[RV] wired correctly?

forward, and [RV] for

 

 

Is parameter F004 properly set?

reverse.

 

 

 

 

Set motor direction in F004.

 

 

 

 

 

Troubleshooting Maintenance and