3–52

“C” Group: Intelligent Terminal Functions

 

 

 

 

Input Function Summary Table

 

 

 

 

 

 

 

 

 

Option

Terminal

Function Name

 

Description

 

 

Code

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

23

PID

PID Disable

ON

Temporarily disables PID loop control. Inverter

 

 

 

 

 

 

output turns OFF as long as PID Enable is active

 

 

 

 

 

 

(A071=01).

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Has no effect on PID loop operation, which

 

 

 

 

 

 

operates normally if PID Enable is active

 

 

 

 

 

 

(A071=01).

 

 

 

 

 

 

 

 

 

24

PIDC

PID Reset

ON

Resets the PID loop controller. The main conse-

 

 

 

 

 

 

quence is that the integrator sum is forced to

 

 

 

 

 

 

zero.

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No effect on PID loop controller

 

 

 

 

 

 

 

 

 

27

UP

Remote Control

ON

Accelerates (increases output frequency) motor

 

 

 

 

UP Function (motor-

 

from current frequency

 

 

 

 

ized speed pot.)

 

 

 

 

 

 

OFF

Output to motor operates normally

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

DWN

Remote Control

ON

Decelerates (decreases output frequency) motor

 

 

 

 

DOWN Function

 

from current frequency

 

 

 

 

(motorized speed

 

 

 

 

 

 

OFF

Output to motor operates normally

Configuring ParametersDrive

 

 

 

pot.)

 

 

 

 

 

 

 

 

 

 

 

 

29

UDC

Remote Control Data

ON

Clears the UP/DWN frequency memory by

 

 

 

 

 

 

Clearing

 

forcing it to equal the set frequency parameter

 

 

 

 

 

 

F001. Setting C101 must be set=00 to enable this

 

 

 

 

 

 

function to work.

 

 

 

 

 

 

 

 

 

 

 

 

OFF

UP/DWN frequency memory is not changed

 

 

 

 

 

 

 

 

 

31

OPE

Operator Control

ON

Forces the source of the output frequency setting

 

 

 

 

 

 

(A001) and the source of the RUN command

 

 

 

 

 

 

(A002) to be from the digital operator

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Source of output frequency set by (A001) and

 

 

 

 

 

 

source of run command set by (A002) is used

 

 

 

 

 

 

 

 

 

50

ADD

ADD frequency

ON

Adds the A145 value (Add Frequency) to the

 

 

 

 

enable

 

output frequency

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Does not add the A145 value to the output

 

 

 

 

 

 

frequency

 

 

 

 

 

 

 

 

 

51

F-TM

Force Terminal

ON

Force inverter to use input terminals for output

 

 

 

 

Mode

 

frequency and Run command sources

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Source of output frequency set by (A001) and

 

 

 

 

 

 

source of Run command set by (A002) is used

 

 

 

 

 

 

 

 

 

52

RDY

Quick Start Enable

ON

Inverter output is always ON (even when motor

 

 

 

 

 

 

rotation has stopped) to improve motor startup

 

 

 

 

 

 

time.

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Inverter output turns OFF normally in Stop

 

 

 

 

 

 

Mode.