2–31

L2002 Inverter

Set the Number of Motor Poles - The motor’s internal winding arrangement determines its number of magnetic poles. The specifications label on the motor usually indicates the number of poles. For proper operation, verify the parameter setting matches the motor poles. Many industrial motors have four poles, corresponding to the default setting in the inverter (H004).

Follow the steps in the table below to verify the motor poles setting and change it if necessary (the table resumes action from the end of the previous table).

 

 

Action

Display

Func./Parameter

 

 

 

 

 

 

 

 

 

 

(Starting point)

 

 

b 0 1 2

Level of electronic thermal setting

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the FUNC.

key.

 

 

b – – –

“B” Group selected

 

 

 

Press the

1

key two times.

H – – –

“H” Group selected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the FUNC.

key.

 

 

H 0 0 3

First “H” parameter

 

 

 

 

 

 

 

 

 

 

Press the

1

key once.

H 0 0 4

Motor poles parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the FUNC.

key.

 

 

4

2 = 2 poles

 

 

4 = 4 poles (default)

 

 

 

 

 

 

6 = 6 poles

 

 

 

 

 

 

8 = 8 poles

 

 

 

 

 

 

 

Press the

1

or

2

key as needed.

4

Set to match your motor (your

display may be different)

 

 

 

 

 

 

 

 

 

 

 

 

Press the STR

key.

 

H 0 0 4

Stores parameter, returns to “H”

 

Group list

 

 

 

 

 

 

 

This step concludes the parameter setups for the inverter. You are almost ready to run the motor for the first time!

TIP: If you became lost during any of these steps, first observe the state of the PRG LED. Then study the “Keypad Navigational Map” on page 2–26 to determine the current state of the keypad controls and display. As long as you do not press the STR key, no parameters will be changed by keypad entry errors. Note that power cycling the inverter causes it to power up Monitor Mode, displaying the value for D001 (output frequency).

The next section will show you how to monitor a particular parameter from the display. Then you will be ready to run the motor.

Installation and

Mounting Inverter