PID Loop Configuration

The inverter’s PID loop algorithm is configurable for various applications.

PID Output Limit - The PID loop controller has a built-in output limit function. This function monitors the difference between the PID setpoint and the loop output (inverter output frequency), measured as a percentage of the full scale range of each. The limit is specified by parameter A078.

When the difference (Setpoint – loop output) is smaller than or equal to the A078 limit value, the loop controller operates in its normal linear range.

When the difference (Setpoint – loop output) is larger than the A078 limit value, the loop controller changes the output frequency as needed so that the difference does not exceed the limit.

The diagram below shows PID setpoint changes and the related output frequency behavior when a limit value in A078 exists.

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Limit imposed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

on output

 

 

 

 

 

A078

Limit value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PID Setpoint

Output frequency A078

Limit value

Output limit

 

 

 

 

 

 

 

Limit imposed

 

 

 

 

 

 

 

 

 

 

 

 

on output

t

Error Inversion - In typical heating loops or ventilation loops, an increase in energy into the process results in an increasing PV. In this case, the Loop Error = (SP – PV). For cooling loops, an increase in energy into the process results in a decreasing PV. In this case, the Loop Error = –(SP – PV). Use A077 to configure the error term.

A077 = 00

 

 

 

 

 

 

A077 = 01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP +

 

Error

 

Freq.

 

SP –

 

Error

 

Freq.

 

PID

 

PID

 

 

 

 

 

 

Calculation

 

 

 

 

 

 

 

 

 

 

Calculation

 

 

 

PV

 

 

 

 

 

 

PV

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PV from process with

 

 

 

PV from process with

 

 

 

 

 

 

 

 

 

 

 

 

positive correlation

 

 

 

 

negative correlation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operations Monitoring and

Other PID-related topics:

“PID Control” on page 3–24

“PID ON/OFF and PID Clear” on page 4–28

“Output Deviation for PID Control” on page 4–42

“PID Second Stage Output” on page 4–46