3–50

“C” Group: Intelligent Terminal Functions

Input Function Summary Table – This table shows all twenty-four intelligent input functions at a glance. Detailed descriptions of these functions, related parameters and settings, and example wiring diagrams are in “Using Intelligent Input Terminals” on page 4–9.

 

 

 

 

Input Function Summary Table

 

 

 

 

 

 

 

 

 

Option

Terminal

Function Name

 

Description

 

 

Code

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

FW

Forward Run/Stop

ON

Inverter is in Run Mode, motor runs forward

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Inverter is in Stop Mode, motor stops

 

 

 

 

 

 

 

 

 

01

RV

Reverse Run/Stop

ON

Inverter is in Run Mode, motor runs reverse

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Inverter is in Stop Mode, motor stops

 

 

 

 

 

 

 

 

 

02

CF1 *1

Multi-speed Select,

ON

Binary encoded speed select, Bit 0, logical 1

 

 

 

 

Bit 0 (LSB)

 

 

 

 

 

 

OFF

Binary encoded speed select, Bit 0, logical 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

CF2

Multi-speed Select,

ON

Binary encoded speed select, Bit 1, logical 1

 

 

 

 

Bit 1

 

 

 

 

 

 

OFF

Binary encoded speed select, Bit 1, logical 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

CF3

Multi-speed Select,

ON

Binary encoded speed select, Bit 2, logical 1

 

Configuring ParametersDrive

 

 

 

Bit 2

 

 

 

 

 

OFF

Binary encoded speed select, Bit 2, logical 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05

CF4

Multi-speed Select,

ON

Binary encoded speed select, Bit 3, logical 1

 

 

 

 

Bit 3 (MSB)

 

 

 

 

 

 

OFF

Binary encoded speed select, Bit 3, logical 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

JG

Jogging

ON

Inverter is in Run Mode, output to motor runs at

 

 

 

 

 

 

jog parameter frequency

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Inverter is in Stop Mode

 

 

 

 

 

 

 

 

 

07

DB

External DC Braking

ON

DC braking will be applied during deceleration

 

 

 

 

 

 

 

 

 

 

 

 

OFF

DC braking will not be applied

 

 

 

 

 

 

 

 

 

08

SET

Set (select) 2nd

ON

The inverter uses 2nd motor parameters for

 

 

 

 

Motor Data

 

generating frequency output to motor. The selec-

 

 

 

 

 

 

tion of 1st or 2nd motor is available only during

 

 

 

 

 

 

Stop Mode.

 

 

 

 

 

 

 

 

 

 

 

 

OFF

The inverter uses 1st (main) motor parameters

 

 

 

 

 

 

for generating frequency output to motor

 

 

 

 

 

 

 

 

 

09

2CH

2-stage Acceleration

ON

Frequency output uses 2nd-stage acceleration

 

 

 

 

and Deceleration

 

and deceleration values

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Frequency output uses standard acceleration and

 

 

 

 

 

 

deceleration values

 

 

 

 

 

 

 

 

 

11

FRS

Free-run Stop

ON

Causes output to turn OFF, allowing motor to

 

 

 

 

 

 

free run (coast) to stop

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Output operates normally, so controlled deceler-

 

 

 

 

 

 

ation stops motor