3–8

“D” Group: Monitoring Functions

Local Monitoring During Network Operation

Configuring

Drive Parameters

 

 

The L2002 inverter’s serial port may be connected to a network or to an external digital operator. During those times, the inverter keypad keys will not function (except for the Stop key). However, the inverter’s 4-digit display still provides the Monitor Mode function, displaying any of the parameters D001 to D007. Function B089, Monitor Display Select for Networked Inverter, determines the particular D00x parameter displayed. Refer to the table below.

B089 Monitor Display Select for Networked Inverter

Option

Monitor

Monitor Function Name

Code

Code

 

 

 

 

 

 

 

01

D001

Output frequency monitor

 

 

 

02

D002

Output current monitor

 

 

 

03

D003

Rotation direction monitor

 

 

 

04

D004

Process variable (PV), PID feedback monitor

 

 

 

05

D005

Intelligent input terminal status

 

 

 

06

D006

Intelligent output terminal status

 

 

 

07

D007

Scaled output frequency monitor

 

 

 

When monitoring the inverter during network operation, please note the following:

The inverter display will monitor D00x functions according to B089 setting when...

the OPE/485 DIP switch is set to the “485” position, or

a device is already connected to the inverter’s serial port at inverter powerup.

During network operation, the inverter keypad will also display error codes for inverter trip events. Use the Stop key or inverter Reset function to clear the error. Refer to “Error Codes” on page 6–5 to interpret the error codes.

The Stop key can be disabled, if you prefer, by using function B087.