L2002 Inverter

3–51

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Function Summary Table

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Option

Terminal

Function Name

 

Description

 

 

 

 

Code

Symbol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

EXT

External Trip

ON

When assigned input transitions OFF to ON,

 

 

 

 

 

 

 

 

inverter latches trip event and displays E12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

No trip event for ON to OFF, any recorded trip

 

 

 

 

 

 

 

 

events remain in history until Reset

 

 

 

 

 

 

 

 

 

 

 

 

 

13

USP

Unattended Start

ON

On powerup, the inverter will not resume a Run

 

 

 

 

 

 

Protection

 

command (mostly used in the US)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

On powerup, the inverter will resume a Run

 

 

 

 

 

 

 

 

command that was active before power loss

 

 

 

 

 

 

 

 

 

 

 

 

 

15

SFT

Software Lock

ON

The keypad and remote programming devices

 

 

 

 

 

 

 

 

are prevented from changing parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

The parameters may be edited and stored

 

 

 

 

 

 

 

 

 

 

 

 

 

16

AT

Analog Input

ON

Terminal [OI] is enabled for current input (uses

 

 

 

 

 

 

Voltage/current

 

terminal [L] for power supply return)

 

 

 

 

 

 

Select

 

 

 

 

 

 

 

 

 

OFF

Terminal [O] is enabled for voltage input (uses

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal [L] for power supply return)

 

 

 

 

 

 

 

 

ParametersDrive

 

 

 

 

 

 

 

 

 

 

18

RS

Reset Inverter

ON

The trip condition is reset, the motor output is

 

 

 

 

 

 

 

turned OFF, and powerup reset is asserted

 

Configuring

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Normal power-ON operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

PTC

PTC Thermistor

ANLG

When a thermistor is connected to terminals [5]

 

 

 

 

 

 

Thermal Protection

 

and [L], the inverter checks for over-

 

 

 

 

 

 

 

 

temperature and will cause trip event and turn

 

 

 

 

 

 

 

 

OFF output to motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPEN

A disconnect of the thermistor causes a trip

 

 

 

 

 

 

 

 

event, and the inverter turns OFF the motor

 

 

 

 

 

 

 

 

 

 

 

 

 

20

STA

Start

ON

Starts the motor rotation

 

 

 

 

 

 

(3-wire interface)

 

 

 

 

 

 

 

 

 

OFF

No change to present motor status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

STP

Stop

ON

Stops the motor rotation

 

 

 

 

 

 

(3-wire interface)

 

 

 

 

 

 

 

 

 

OFF

No change to present motor status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

F/R

FWD, REV

ON

Selects the direction of motor rotation: ON =

 

 

 

 

 

 

(3-wire interface)

 

FWD. While the motor is rotating, a change of

 

 

 

 

 

 

 

 

F/R will start a deceleration, followed by a

 

 

 

 

 

 

 

 

change in direction.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Selects the direction of motor rotation: OFF =

 

 

 

 

 

 

 

 

REV. While the motor is rotating, a change of F/

 

 

 

 

 

 

 

 

R will start a deceleration, followed by a change

 

 

 

 

 

 

 

 

in direction.