“A” Group: Standard Functions

The inverter has other control sources that can temporarily override the parameter A001 setting, forcing a different output frequency source. The following table lists all frequency source setting methods and their relative priority (“1” is the highest priority).

Priority

A001 Frequency Source Setting Method

Refer to page...

 

 

 

 

 

 

1

[CF1] to [CF4] Multi-speed terminals

4–13

 

 

 

2

[OPE] Operator Control intelligent input

4–31

 

 

 

3

[F-TM] intelligent input

4–33

 

 

 

4

[AT] terminal

4–23

 

 

 

5

TM/PRG DIP Switch - (if switch is in “TM” position)

3–11

 

 

 

6

A001 Frequency source setting

3–10

 

 

 

The inverter also has other control sources that can temporarily override the parameter A002 setting, forcing a different Run command source. The following table lists all Run command setting methods and their relative priority (“1” is the highest priority).

 

 

Priority

A002 Run Command Setting Method

Refer to page...

 

 

 

 

 

 

 

 

 

 

Configuring ParametersDrive

 

1

[OPE] Operator Control intelligent input

4–31

 

 

 

 

 

2

[F-TM] intelligent input

4–33

 

 

 

 

 

 

 

 

 

3

TM/PRG DIP Switch - (if switch is in “TM” position)

3–11

 

 

 

 

 

 

 

4

A002 Run command source setting

3–10