3–38

“B” Group: Fine Tuning Functions

Configuring

Drive Parameters

 

 

 

 

“B” Function

Run

 

Defaults

 

 

 

 

 

Mode

 

 

 

Func.

Name /

 

–FE(F)

–FU

 

Description

Edit

Units

Code

SRW Display

Lo Hi

(EU)

(USA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B021

Overload restriction

Select the operating mode

✘ ✔

01

01

 

operation mode

during overload conditions,

 

 

 

 

 

 

 

three options, option codes:

 

 

 

 

 

OL Mode

ON

 

 

 

 

 

00... Disabled

 

 

 

 

 

 

 

 

 

 

 

B221

Overload restriction

01... Enabled for acceleration

✘ ✔

01

01

 

operation mode, 2nd

and constant speed

 

 

 

 

 

motor

 

02... Enabled for constant

 

 

 

 

 

 

 

speed only

 

 

 

 

 

2OL Mode

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B022

Overload restriction

Sets the level for overload

✘ ✔

Rated current x

A

 

setting

 

restriction, between 10% and

 

1.5

 

 

 

 

150% of the rated current of

 

 

 

 

 

OL LVL

002.40A

 

 

 

 

 

the inverter, setting resolution

 

 

 

 

B222

Overload restriction

is 1% of rated current. This

✘ ✔

Rated current x

A

 

setting, 2nd motor

parameter monitors (read-only)

 

1.5

 

 

 

 

the [O]–[L] input when that

 

 

 

 

 

2OL LVL

002.40A

 

 

 

 

 

input is the overload restriction

 

 

 

 

 

 

 

source (B028/B228 = 01).

 

 

 

 

 

 

 

 

 

 

 

B023

Deceleration rate at

Sets the deceleration rate when

✘ ✔

1.0

30.0

sec.

 

overload restriction

inverter detects overload, range

 

 

 

 

 

 

 

is 0.1 to 30.0, resolution is 0.1.

 

 

 

 

 

OL Cnst

0001.0s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B223

Deceleration rate at

Sets the deceleration rate when

✘ ✔

1.0

30.0

sec.

 

overload restriction,

inverter detects overload, range

 

 

 

 

 

2nd motor

 

is 0.1 to 30.0, resolution is 0.1.

 

 

 

 

 

 

 

 

 

 

 

 

2OL Cnst 0001.0s

 

 

 

 

 

 

 

 

 

 

 

 

B028

Overload restriction

Two options; select codes:

✘ ✔

00

00

sec.

 

source selection

00... B022/B222 setting level

 

 

 

 

 

 

 

01... [O]–[L] analog input

 

 

 

 

 

OL L-Slct

C022

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B228

Overload restriction

Two options; select codes:

✘ ✔

00

00

sec.

 

source selection, 2nd

00... B022/B222 setting level

 

 

 

 

 

motor

 

01... [O]–[L] analog input

 

 

 

 

 

 

 

 

 

 

 

 

2OL L-Slct C022