B–30

ModBus Data Listing

 

 

Holding Registers for “A” Group Standard Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Network Data

 

 

Func.

 

 

 

 

 

 

 

 

 

Name

R/W

 

Description

Register

 

 

 

Code

 

Range

Res.

 

 

 

 

 

 

 

 

 

 

 

 

 

hex

dec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A076

PV source setting

R/W

Selects source of Process

106Dh

04205

0, 1, 2, 3

 

 

 

 

Variable (PV), option codes:

 

 

 

 

 

 

 

 

00

...[OI] terminal (current in)

 

 

 

 

 

 

 

 

01

...[O] terminal (voltage in)

 

 

 

 

 

 

 

 

02

...Network

 

 

 

 

 

 

 

 

03

...Calculate function output

 

 

 

 

 

 

 

 

 

 

 

 

 

B

A077

Reverse PID action

R/W

Two option codes:

106Eh

04206

0, 1

Appendix

 

 

 

00

...PID input = SP – PV

 

 

 

 

 

 

 

01

...PID input = –(SP – PV)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A078

PID output limit

R/W

Sets the limit of PID output as

106Fh

04207

0 to 1000

0.1 %

 

 

 

 

percent of full scale,

 

 

 

 

 

 

 

 

range is 0.0 to 100.0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A081

AVR function select

R/W

Automatic (output) voltage

1070h

04208

0, 1, 2

 

 

 

 

regulation, selects from three

 

 

 

 

 

 

 

 

type of AVR functions, three

 

 

 

 

 

 

 

 

option codes:

 

 

 

 

 

 

 

 

00

...AVR enabled

 

 

 

 

 

 

 

 

01

...AVR disabled

 

 

 

 

 

 

 

 

02

...AVR enabled except

 

 

 

 

 

 

 

 

during deceleration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A082

AVR voltage select

R/W

200V class inverter settings:

1071h

04209

0 to 5

 

 

 

 

00

...200

 

 

 

 

 

 

 

 

01

...215

 

 

 

 

 

 

 

 

02

...220

 

 

 

 

 

 

 

 

03

...230

 

 

 

 

 

 

 

 

04

...240

 

 

 

 

 

 

 

 

400V class inverter settings:

 

 

 

 

 

 

 

 

00

...380

 

 

 

 

 

 

 

 

01

...400

 

 

 

 

 

 

 

 

02

...415

 

 

 

 

 

 

 

 

03

...440

 

 

 

 

 

 

 

 

04

...460

 

 

 

 

 

 

 

 

05

...480

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A092

Acceleration (2) time

R/W

Duration of 2nd segment of

1074h

04212

1 to

0.1 sec

 

(high)

setting

 

acceleration, range is:

 

 

300000

 

 

 

 

 

0.01 to 3000 sec.

 

 

*1

 

 

A092

 

R/W

1075h

04213

 

 

(low)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A292

Acceleration (2) time

R/W

Duration of 2nd segment of

1518h

05400

1 to

0.1 sec

 

(high)

setting, (2nd motor)

 

acceleration, 2nd motor,

 

 

300000

 

 

 

 

 

range is: 0.01 to 3000 sec

 

 

*1

 

 

A292

 

R/W

1519h

05401

 

 

(low)