B–5

L2002 Inverter

6.Inverter Parameter Setup - The inverter has several settings related to ModBus communications. The table below lists them together. The Required column indicates which parameters must be set properly to allow communications. You may need to refer to the host computer documentation in order to match some of its settings.

Func.

Name

Required

 

Settings

 

 

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A001

Frequency source setting

00... Keypad potentiometer

 

 

 

 

 

01

... Control terminal

 

 

 

 

 

02

... Function F001 setting

 

 

 

 

 

03

...ModBus network input

 

 

 

 

 

 

 

 

 

10

... Calculate function output

 

 

 

 

 

 

 

 

A002

Run command source setting

01... Control terminal

 

Appendix

 

networked inverter

 

02... Output current monitor

 

 

 

 

02

... Run key on keypad, or digital operator

 

 

 

 

 

03

...ModBus network input

 

 

B089

Monitor display select for

01... Output frequency monitor

 

 

 

 

 

03

... Rotation direction monitor

 

B

 

 

 

04

... Process variable (PV), PID feedback

 

 

 

 

 

monitor

 

 

 

 

 

05

... Intelligent input terminal status

 

 

 

 

 

06

... Intelligent output terminal status

 

 

 

 

 

07

... Scaled output frequency monitor

 

 

 

 

 

 

 

 

C071

Communication speed selection

04... 4800 bps

 

 

 

 

 

05

... 9600 bps

 

 

 

 

 

06

... 19200 bps

 

 

 

 

 

 

 

 

C072

Node allocation

Network address, range is 1 to 32

 

 

 

 

 

 

 

 

C074

Communication parity selection

00... No parity

 

 

 

 

 

01

... Even parity

 

 

 

 

 

02

... Odd parity

 

 

 

 

 

 

 

 

C075

Communication stop bit selection

Range is 1 to 2

 

 

 

 

 

 

 

 

C076

Communication error select

00... Trip (error code E60)

 

 

 

 

 

01

... Decelerate to a stop and trip (error code

 

 

 

 

 

E60)

 

 

 

 

 

02

... Disable

 

 

 

 

 

03

... Free run stop (coasting)

 

 

 

 

 

04

... Decelerate to a stop

 

 

 

 

 

 

 

 

C077

Communication error time-out

Comm. watchdog timer period,

 

 

 

 

 

range is 0.00 to 99.99 sec.

 

 

 

 

 

 

 

 

C078

Communication wait time

Time the inverter waits after receiving a

 

 

 

 

 

message before it transmits.

 

 

 

 

 

Range is 0. to 1000. ms

 

 

 

 

 

 

 

 

 

NOTE: When you edit and store any of the parameters above, the inverter causes it to take effect immediately. ModBus transmission occurs only after you set the OPE/485 DIP switch to the “485” position and turn on the inverter. Note that parameters C071 to C078 cannot be changed via the network. To edit them, reconnect the inverter keypad (or other digital operator) and edit the parameters.