2–30

Using the Front Panel Keypad

Inverter Mounting

and Installation

 

 

 

 

Action

Display

Func./Parameter

 

 

 

 

 

 

 

 

 

 

(Starting point)

 

 

A 0 0 3

Base frequency setting

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the

1

key and hold until-->A 0 8 2

AVR voltage select

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the FUNC. key.

 

2 3 0

Default values for AVR voltage:

 

200V class = 230VAC

 

 

 

 

 

or

400V class = 400VAC (–xxxFEF)

 

 

 

 

 

4 0 0

400V class = 460VAC (–xxxFU)

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the

1

or

2

key as needed.

2 1 5

Set to your motor specs (your

display may be different)

 

 

 

 

 

 

 

 

 

 

 

 

Press the STR

key.

 

A 0 8 2

Stores parameter, returns to “A”

 

Group list

 

 

 

 

 

 

 

Set the Motor Current - The inverter has thermal overload protection that is designed to protect the inverter and motor from overheating due to an excessive load. The inverter’s uses the motor’s current rating to calculate the time-based heating effect. This protection depends on using the correct current rating for your motor. The level of electronic thermal setting, parameter B012, is adjustable from 20% to 120% of the inverter’s rated current. A proper configuration will also help prevent unnecessary inverter trip events.

Read the motor’s current rating on its manufacturer’s nameplate. Then follow the steps below to configure the inverter’s thermal overload protection setting.

 

 

Action

Display

Func./Parameter

 

 

 

 

 

 

 

 

 

 

(Starting point)

 

 

A 0 8 2

Base frequency setting

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the FUNC.

key.

 

 

A – – –

“A” Group selected

 

 

 

Press the

1

key.

 

 

b – – –

“B” Group selected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the FUNC.

key.

 

 

b 0 0 1

First “B” Group parameter

 

 

selected

 

 

 

 

 

 

 

Press the

1

key and hold until-->

b 0 1 2

Level of electronic thermal setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the FUNC.

key.

 

1.60

Default value will be 100% of

 

inverter rated current.

 

 

 

 

 

 

 

Press the

1

or

2

key as needed.

1.80

Set to your motor specs (your

display may be different)

 

 

 

 

 

 

 

 

 

 

 

 

Press the STR

key.

 

B 0 1 2

Stores parameter, returns to “B”

 

Group list