3–62

“C” Group: Intelligent Terminal Functions

Configuring

Drive Parameters

 

 

 

 

“C” Function

Run

 

Defaults

 

 

 

 

 

Mode

 

 

 

Func.

Name /

 

 

–FE(F)

–FU

 

 

Description

Edit

Units

Code

SRW Display

Lo Hi

(EU)

(USA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C143

Logic function select

Applies a logic function to

✘ ✘

00

00

 

 

 

calculate [LOG] output state,

 

 

 

 

 

LogicOPE

AND

 

 

 

 

 

three options:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00... [LOG] = A AND B

 

 

 

 

 

 

 

01... [LOG] = A OR B

 

 

 

 

 

 

 

02... [LOG] = A XOR B

 

 

 

 

 

 

 

 

 

 

 

 

Output Signal ON/OFF Delay Function - Intelligent outputs including terminals [11], [12], and the output relay, have configurable signal transition delays. Each output can delay either the OFF-to-ON or ON-to-OFF transitions, or both. Signal transition delays are variable from 0.1 to 100.0 seconds. This feature is useful in applications that must tailor inverter output signals to meet timing requirements of certain external devices.

 

 

“C” Function

Run

 

Defaults

 

 

 

 

 

Mode

 

 

 

Func.

Name /

 

–FE(F)

–FU

 

Description

Edit

Units

Code

SRW Display

Lo Hi

(EU)

(USA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C144

Terminal [11] ON delay

Range is 0.0 to 100.0 sec.

✘ ✔

0.0

0.0

sec.

 

 

 

 

 

 

 

 

 

DLAY 11

0000.0s

 

 

 

 

 

 

 

 

 

 

 

 

C145

Terminal [11] OFF

Range is 0.0 to 100.0 sec.

✘ ✔

0.0

0.0

sec.

 

delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOLD 11

0000.0s

 

 

 

 

 

 

 

 

 

 

 

 

C146

Terminal [12] ON delay

Range is 0.0 to 100.0 sec.

✘ ✔

0.0

0.0

sec.

 

 

 

 

 

 

 

 

 

DLAY 12

0000.0s

 

 

 

 

 

 

 

 

 

 

 

 

C147

Terminal [12] OFF

Range is 0.0 to 100.0 sec.

✘ ✔

0.0

0.0

sec.

 

delay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOLD 12

0000.0s

 

 

 

 

 

 

 

 

 

 

 

 

C148

Output relay ON delay

Range is 0.0 to 100.0 sec.

✘ ✔

0.0

0.0

sec.

 

 

 

 

 

 

 

 

 

DLAY RY

0000.0s

 

 

 

 

 

 

 

 

 

 

 

 

C149

Output relay OFF delay

Range is 0.0 to 100.0 sec.

✘ ✔

0.0

0.0

sec.

 

 

 

 

 

 

 

 

 

HOLD RY

0000.0s

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: If you are using the output terminal OFF delay feature (any of C145, C147, C149 > 0.0 sec.), the [RS] (Reset) terminal affects the ON-to-OFF transition slightly. Normally (without using OFF delays), the [RS] input causes the motor output and the logic outputs to turn OFF together, immediately. However, when any output uses an OFF delay, then after the [RS] input turns ON, that output will remain ON for an additional 1 sec. period (approximate) before turning OFF.