4–33

L2002 Inverter

Force Terminal Mode

The purpose of this intelligent input is to allow a device to force the inverter to allow control of the following two parameters via the control terminals:

A001 - Frequency source setting (01 = control terminals [FW] and [RV])A002 - Run command source setting (01 = control terminals [O] or [OI])

Some applications will require one or both settings above to use a source other than the terminals. You may prefer to normally use the inverter’s keypad and potentiometer, or to use the ModBus network for control, for example. However, an external device can turn ON the [F-TM] input to force the inverter to (temporarily) allow control (frequency source and Run command) via control terminals. When the [F-TM] input is OFF, then the inverter uses the regular sources specified by A001 and A002 again.

Option

Terminal

Function Name

Input

 

 

Description

Code

Symbol

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51

F-TM

Force Terminal

ON

Forces A001=01 (frequency source setting =

 

 

Mode

 

control terminal), and

 

 

 

 

A002=01(Run command source setting = control

 

 

 

 

terminal)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

Inverter applies the user setting for A001 and

 

 

 

 

A002 normally

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for inputs:

C001, C002, C003, C004,

Example (requires input configuration—see

 

 

C005

 

page 3–47):

Required settings:

A001, A002

 

 

 

 

F-TM

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

L

5

4

3

2

1

PCS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When changing the [F-TM] state during Run Mode

(inverter is driving the motor), the inverter will stop the motor before the new [F-TM] state takes effect.

See I/O specs on page 4–6.