4–17

L2002 Inverter

Set Second Motor and Special-Set Second Motor

If you assign the [SET] or [S-ST] function to an intelligent input terminal, you can select between two sets of motor parameters. The second parameters store an alternate set of motor characteristics. Two type of inputs are available:

Set Second Motor - The inverter can select a different motor only in Stop Mode.

Special-Set Second Motor - The inverter can select a different motor in either Stop Mode or Run Mode. The following parameter pairs can be alternately selected during Run Mode: A020/A220, F002/F202, F003/F203, A042/A242, A043/A243, A061/ A261, A062/A262, A092/A292, A093/A293, A094/A294, A095/A295, A096/A296

When the terminal [SET] or [S-ST] is turned ON, the inverter will use the second set of parameters to generate the frequency output to the motor. When changing the state of the [SET] input terminal, the change will not take effect until the inverter is stopped.

When you turn ON the [SET] or [S-ST] input, the inverter operates per the second set of parameters. When the terminal is turned OFF, the output function returns to the original settings (first set of motor parameters). Refer to “Configuring the Inverter for Multiple Motors” on page 4–58 for details.

Option

Terminal

Function Name

Input

 

 

Description

Code

Symbol

State

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

08

SET

Set (select) 2nd

ON

causes the inverter to use the 2nd set of motor

 

 

Motor Data

 

parameters for generating the frequency output

 

 

 

 

to motor. The selection of 1st or 2nd motor is

 

 

 

 

available only in Stop Mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

causes the inverter to use the 1st (main) set of

 

 

 

 

motor parameters for generating the frequency

 

 

 

 

output to motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

53

S-ST

Special-Set (select)

ON

causes the inverter to use the 2nd set of motor

 

 

2nd Motor Data

 

parameters for generating the frequency output

 

 

 

 

to motor. The selection of 1st or 2nd motor is

 

 

 

 

available in Stop Mode or Run Mode.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

causes the inverter to use the 1st (main) set of

 

 

 

 

motor parameters for generating the frequency

 

 

 

 

output to motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valid for inputs:

C001, C002, C003, C004,

Example (requires input configuration—see

 

 

C005

 

page 3–47):

Required settings:

(none)

 

 

 

 

 

SET

 

 

 

 

(or S-ST)

 

 

 

 

 

 

 

Notes:

 

 

 

 

L

5

4

3

2

1

PCS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the terminal state for [SET] is changed while the

inverter is running, the inverter continues using the current set of parameters until the inverter is stopped.

You cannot configure the inverter to use [SET] and

[S-ST] terminals at the same time.

See I/O specs on page 4–6.