B–19

L2002 Inverter

ModBus Data Listing

ModBus Coil List

The following tables list the primary coils for the inverter interface to the network. The table legend is given below.

Coil Number - The network register address offset for the coil, in hex and decimal. Actual network address is 30001 + offset. The coil data is a single bit (binary) value.

Name - The functional name of the coil

R/W - The read-only (R) or read-write (R/W) access permitted to the inverter data

Description - The meaning of each of the states of the coils

 

 

 

 

 

 

 

Appendix

 

 

 

List of Coil Numbers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Coil Number

Name

R/W

 

Description

 

 

 

 

 

 

 

 

 

 

hex

dec.

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0000h

00000

(Reserved)

R

 

 

 

 

 

 

 

 

 

 

 

0001h

00001

Run command

R/W

0

.... Stop

 

 

 

 

 

 

1

.... Run (enabled when A003=03)

 

 

 

 

 

 

 

 

 

 

0002h

00002

FW/REV command

R/W

0

.... REV

 

 

 

 

 

 

1

.... FW (enabled when A003=03)

 

 

 

 

 

 

 

 

 

 

0003h

00003

External trip (EXT)

R/W

0

.... No trip event

 

 

 

 

 

 

1

.... Trip occurred

 

 

 

 

 

 

 

 

 

 

0004h

00004

Trip reset (RS)

R/W

0

.... No reset condition

 

 

 

 

 

 

1

.... Reset

 

 

 

 

 

 

 

 

 

 

0005h

00005

(Reserved)

R

 

 

 

 

 

 

 

 

 

 

 

0006h

00006

(Reserved)

R

 

 

 

 

 

 

 

 

 

 

 

0007h

00007

Intelligent input terminal 1

R/W

0

.... OFF *1

 

 

 

 

 

 

1

.... ON

 

 

0008h

00008

Intelligent input terminal 2

R/W

 

 

 

 

 

 

 

 

 

 

0009h

00009

Intelligent input terminal 3

R/W

 

 

 

 

 

 

 

 

 

 

 

 

000Ah

00010

Intelligent input terminal 4

R/W

 

 

 

 

 

 

 

 

 

 

 

 

000Bh

00011

Intelligent input terminal 5

R/W

 

 

 

 

 

 

 

 

 

 

 

 

000Dh

00013

(Not used)

 

 

 

 

 

 

 

 

 

 

 

000Eh

00014

Run/Stop status

R

0

.... Stop (corresponds to D003

 

 

 

 

 

 

monitor)

 

 

 

 

 

 

1

.... Run

 

 

 

 

 

 

 

 

 

 

000Fh

00015

FW/REV status

R

0

.... FW

 

 

 

 

 

 

1

.... RV

 

 

 

 

 

 

 

 

 

 

0010h

00016

Inverter ready

R

0

.... Not ready

 

 

 

 

 

 

1

.... Ready

 

 

 

 

 

 

 

 

 

 

0011h

00017

(Reserved)

R

 

 

 

 

 

 

 

 

 

 

 

0012h

00018

(Reserved)

R