2–17

L2002 Inverter

Determining Wire and Fuse Sizes

The maximum motor currents in your application determines the recommended wire size. The following table gives the wire size in AWG. The “Power Lines” column applies to the inverter input power, output wires to the motor, the earth ground connection, and any other component shown in the “Basic System Description” on page 2–7. The “Signal Lines” column applies to any wire connecting to the two green 8-position connectors just inside the front panel half-door.

Motor Output

 

 

Wiring

 

Applicable

(kW/HP)

Inverter Model

 

 

equipment

 

 

 

 

 

 

 

 

 

 

 

kW

HP

 

 

Power Lines

Signal Lines

Fuse / Breaker

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

1/4

L200-002NFE(F)2/NFU2

 

 

 

 

 

 

 

 

 

0.4

1/2

L200-004NFE(F)2/NFU2 AWG16 / 1.3 mm2

 

10A

0.55

3/4

L200-005NFE(F)2

 

 

 

 

 

 

 

 

 

0.75

1

L200-007NFE(F)2/NFU2

 

 

 

 

 

 

AWG14 / 2.1 mm2

 

15A

 

 

 

 

 

1.11 1/2 L200-011NFE(F)2

1.5

2

L200-015NFE(F)2/NFU2

AWG12 / 3.3 mm2

 

20A (single ph.)

 

 

 

 

 

15A (three ph.)

 

 

 

 

 

 

2.2

3

L200-022NFE(F)2/NFU2

AWG10 / 5.3 mm2

 

30A (single ph.)

 

 

 

 

 

20A (three ph.)

 

 

 

 

 

 

3.7

5

L200-037LFU2

AWG10 / 5.3 mm2

18 to 28 AWG /

30A

 

 

 

 

0.14 to 0.75 mm2

 

5.5

7 1/2

L200-055LFU2

AWG10 / 5.3 mm2

40A

shielded wire

 

 

 

 

 

7.5

10

L200-075LFU2

AWG8 / 8.4 mm2

(see Note 4)

50A

0.4

1/2

L200-004HFE(F)2/HFU2

 

 

3A

 

 

 

 

 

 

0.75

1

L200-007HFE(F)2/HFU2

AWG16 / 1.3 mm2

 

6A

 

 

 

 

 

1.5

2

L200-015HFE(F)2/HFU2

 

10A

 

 

 

 

 

 

 

2.2

3

L200-022HFE(F)2/HFU2

 

 

 

 

 

 

 

 

 

 

 

3.0

4

L200-030HFE(F)2

AWG14 / 2.1 mm2

 

15A

 

 

 

 

4.0

5

L200-040HFE(F)2/HFU2

 

 

 

 

 

 

 

 

 

 

5.5

7 1/2

L200-055HFE(F)2/HFU2

AWG12 / 3.3 mm2

 

20A

 

 

 

 

 

7.5

10

L200-075HFE(F)2/HFU2

 

25A

 

 

Note 1: Field wiring must be made by a UL-listed and CSA-certified closed-loop terminal connector sized for the wire gauge involved. Connector must be fixed by using the crimping tool specified by the connector manufacturer.

Note 2: Be sure to consider the capacity of the circuit breaker to be used.

Note 3: Be sure to use a larger wire gauge if power line length exceeds 66 ft. (20m).

Note 4: Use 18 AWG / 0.75 mm2 wire for the alarm signal wire ([AL0], [AL1], [AL2] terminals).

Note 5: The inverter’s input power wiring must include UL Listed, dual-element,

600V fuses, or UL Listed, inverse-time, 600V circuit breakers.