B–40

ModBus Data Listing

 

 

 

“C” Group Intelligent Terminal Functions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Network Data

 

 

Func.

 

 

 

 

 

 

 

 

Name

R/W

Description

Register

 

 

 

Code

Range

Res.

 

 

 

 

 

 

 

 

 

 

 

hex

dec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C041

Overload level setting

R/W

Sets the overload signal level

1124h

04388

0 to

0.01 %

 

 

 

 

between 0% and 200% (from

 

 

20000

 

 

 

 

 

0 to two times the rated

 

 

 

 

 

 

 

 

current of the inverter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C042

Frequency arrival

R/W

Sets the frequency arrival

1126h

04390

0 to 4000

0.1 Hz

 

 

setting for acceleration

 

setting threshold for the

 

 

*1

 

B

 

 

 

output frequency during

 

 

 

 

Appendix

 

 

 

acceleration, range is 0.0 to

 

 

 

 

 

 

 

400.0 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C043

Arrival frequency

R/W

Sets the frequency arrival

1128h

04392

0 to 4000

0.1 Hz

 

 

setting for deceleration

 

setting threshold for the

 

 

 

 

 

 

 

 

output frequency during

 

 

 

 

 

 

 

 

deceleration, range is 0.0 to

 

 

 

 

 

 

 

 

400.0 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C044

PID deviation level

R/W

Sets the allowable PID loop

1129h

04393

0 to 1000

0.1 %

 

 

setting

 

error magnitude (absolute

 

 

 

 

 

 

 

 

value), SP - PV, range is 0.0 to

 

 

 

 

 

 

 

 

100%, resolution is 0.1%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C052

PID FBV function high

R/W

When the PV exceeds this

112Eh

04398

0 to 1000

0.1 %

 

 

limit

 

value, the PID loop turns OFF

 

 

 

 

 

 

 

 

the PID Second Stage Output,

 

 

 

 

 

 

 

 

range is 0.0 to 100.0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C053

PID FBV function low

R/W

When the PV goes below this

112Fh

04399

0 to 1000

0.1 %

 

 

limit

 

value, the PID loop turns ON

 

 

 

 

 

 

 

 

the PID Second Stage Output,

 

 

 

 

 

 

 

 

range is 0.0 to 100.0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C071

Communication speed

 

1138h

04408

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C072

Node allocation

 

1139h

04409

 

 

 

 

 

 

 

 

 

 

C074

Communication parity

NOTE: These network

113Bh

04411

 

 

selection

 

 

 

 

 

 

 

 

settings are not accessible to

 

 

 

 

 

 

 

 

 

 

 

 

 

C075

Communication stop bit

ModBus. Use the inverter

113Ch

04412

 

 

selection

 

keypad or digital operator to

 

 

 

 

 

 

 

 

edit. Refer to “Network

 

 

 

 

 

C076

Communication error

113Dh

04413

 

Communication Settings”

 

 

select

 

 

 

 

 

 

 

 

on page 3–58.

 

 

 

 

 

 

 

 

 

 

 

 

 

C077

Communication error

 

113Eh

04414

 

 

time-out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C078

Communication wait

 

113Fh

04415

 

 

time