2–29

L2002 Inverter

Set the Motor Base Frequency - The motor is designed to operate at a specific AC frequency. Most commercial motors are designed for 50/60 Hz operation. First, check the motor specifications. Then follow the steps below to verify the setting or correct it for your motor. DO NOT set it greater than 50/60 Hz unless the motor manufacturer specifically approves operation at the higher frequency.

 

 

Action

Display

Func./Parameter

 

 

 

 

 

 

 

 

 

 

(Starting point)

 

 

A 0 0 2

Run command source setting

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the

1

key once.

A 0 0 3

Base frequency setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press the FUNC. key.

 

6 0

Default value for base frequency.

 

US = 60 Hz, Europe = 50 Hz.

 

 

 

 

 

or

 

 

 

 

 

 

5 0

 

 

 

 

 

 

 

 

Press the

1

or

2

key as needed.

6 0

Set to your motor specs (your

display may be different)

 

 

 

 

 

 

 

 

 

 

 

 

Press the STR

key.

 

A 0 0 3

Stores parameter, returns to “A”

 

Group list

 

 

 

 

 

 

 

CAUTION: If you operate a motor at a frequency higher than the inverter standard default setting (50Hz/60Hz), be sure to check the motor and machine specifications with the respective manufacturer. Only operate the motor at elevated frequencies after getting their approval. Otherwise, there is the danger of equipment damage.

Set the AVR Voltage Setting - The inverter has an Automatic Voltage Regulation (AVR) function. It adjusts the output voltage to match the motor’s nameplate voltage rating. The AVR smooths out fluctuations in the input power source, but note that it does not boost the voltage in the event of a brown-out. Use the AVR setting (A082) that most closely matches the one for your motor.

200V Class: 200 / 215 / 220 / 230 / 240 VAC

400V Class: 380 / 400 / 415 / 440 / 460 / 480 VAC

TIP: If you need to scroll through a function or parameter list, press and hold the 1 or

2key to auto-increment through the list.

To set the motor voltage, follow the steps on the following page.

Installation and