B–34

ModBus Data Listing

Appendix B

The following table lists the holding registers for the “B” Group Fine Tuning Functions.

“B” Group Fine Tuning Functions

 

 

 

 

 

 

Network Data

 

Func.

 

 

 

 

 

 

 

 

Name

R/W

 

Description

Register

 

 

Code

 

Range

Res.

 

 

 

 

 

 

 

 

 

 

 

hex

dec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B001

Selection of automatic

R/W

Select inverter restart method,

10A5h

04261

0, 1, 2, 3

 

restart mode

 

four option codes:

 

 

 

 

 

 

 

00

... Alarm output after trip,

 

 

 

 

 

 

 

 

no automatic restart

 

 

 

 

 

 

 

01

... Restart at 0Hz

 

 

 

 

 

 

 

02

... Resume operation after

 

 

 

 

 

 

 

 

frequency matching

 

 

 

 

 

 

 

03

... Resume previous freq.

 

 

 

 

 

 

 

after freq. matching, then

 

 

 

 

 

 

 

decelerate to stop and display

 

 

 

 

 

 

 

trip info.

 

 

 

 

 

 

 

 

 

 

 

 

B002

Allowable under-

R/W

The amount of time a power

10A6h

04262

3 to 250

0.1 sec

 

voltage power failure

 

input under-voltage can occur

 

 

 

 

 

time

 

without tripping the power

 

 

 

 

 

 

 

failure alarm. Range is 0.3 to

 

 

 

 

 

 

 

25 sec. If under-voltage exists

 

 

 

 

 

 

 

longer than this time, the

 

 

 

 

 

 

 

inverter trips, even if the

 

 

 

 

 

 

 

restart mode is selected.

 

 

 

 

 

 

 

 

 

 

 

 

B003

Retry wait time before

R/W

Time delay after under-

10A7h

04263

3 to

0.1 sec

 

motor restart

 

voltage condition goes away,

 

 

1000

 

 

 

 

before the inverter runs motor

 

 

 

 

 

 

 

again.

 

 

 

 

 

 

 

Range is 0.3 to 100 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

B004

Instantaneous power

R/W

Two option codes:

10A8h

04264

0, 1

 

failure / under-voltage

 

00

... Disable

 

 

 

 

 

trip alarm enable

 

01

... Enable

 

 

 

 

 

 

 

 

 

 

 

 

B005

Number of restarts on

R/W

Two option codes:

10A9h

04265

0, 1

 

power failure / under-

 

00

... Restart 16 times

 

 

 

 

 

voltage trip events

 

01

... Always restart

 

 

 

 

 

 

 

 

 

 

 

 

B012

Level of electronic

R/W

Set a level between 20% and

10AD

04269

2000 to

0.01%

 

thermal setting

 

120% for the rated inverter

h

 

12000

 

 

 

 

current

 

 

 

 

B212

Level of electronic

R/W

1526h

05414

 

 

 

thermal setting, 2nd

 

 

 

 

 

 

 

 

motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B013

Electronic thermal

R/W

Select from two curves,

10AEh

04270

0, 1, 2

 

characteristic

 

option codes: *1

 

 

 

 

 

 

 

00

... Reduced torque 1

 

 

 

 

B213

Electronic thermal

R/W

1527h

05415

 

 

01... Constant torque

 

 

 

characteristic, 2nd

 

02

... Reduced torque 2

 

 

 

 

 

motor