Chapter 3: Installation

Connect Power - CMS (14 slot), DC only)

Power Requirements

Power requirements for connecting the DC power to the Tenor CMS are as follows:

Voltage range -42V to -60V DC

Maximum current: 20 Amps

Customer must provide upstream short circuit (over current) protection for each DC power feed in case of accidental wire crossing or reversed polarity connection.

Material Requirements

Stranded copper wire that is a minimum of 14 AWG (American Wire Gage) or a maximum of 10 AWG (min 2.0 mm2, max 5.0 mm2) and insulation rated at a minimum of 90° C or better must be used for all wires to the power inlets.

Connect Power

WARNING: Before making any changes to the wiring of your Tenor CMS, turn off both circuit breakers and open the upstream disconnect switches at the source of the DC power feeds.

NOTE: The electrical installation must comply with the National Electrical Code 1996 or other country specific electrical installation codes.

Figure 3-8DC Power Panel (located on bottom rear of chassis)

Circuit Breaker

 

 

 

 

Power Receptacle

Power Receptacle

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tenor CMS - Rear View

 

Power plug

Power plug

Power

plug

Power plug

The top circuit breaker controls the left power inlet and the bottom circuit breaker controls the right power inlet. See Figure 3-8. Each circuit breaker has a dual colored rocker. Pushing down on the left side of the breaker (ON/1) will close the switch and expose a red indicator that shows the user that the contacts are made (closed). To open the contacts, push down on the right side (Off/O).

1.Check to ensure the source of both DC feeds to the CMS are turned off and the circuit breakers are in the off position prior to making or removing any power wire connections.

2.Beginning with the wire attached to Earth Ground, strip away 0.25 in. (7.0 mm) of insulation. See Figure 3-9.

P/N 480-0005-00-15

3-11