Table 47 on page 104 specifies the environmental conditions required for normal Services Router operation. In addition, the site must be as dust-free as possible. Dust can clog air intake vents, reducing cooling system efficiency. Check vents frequently, cleaning them as necessary.

Table 47: Router Environmental Tolerances

Description

Value

Altitude

No performance degradation to 10,000 ft (3048 m)

Relative humidity

Normal operation ensured in relative humidity range of 5% to

 

90%, noncondensing

Temperature

Normal operation ensured in temperature range of 0°C (32°F) to

 

40°C (104°F)

 

Non-operating storage temperature in shipping carton:

 

–40°C (–40°F) to 70°C (158°F)

Seismic

Designed to meet Telcordia Technologies Zone 4 earthquake

 

requirements

Maximum thermal output

J2320 chassis: 1091 BTU/hour (320 W)

 

J2350 chassis: 1195 BTU/hour (350 W)

 

J4350 chassis: 1092 BTU/hour (320 W)

 

J6350 chassis: 1126 BTU/hour (330 W)

Fire Safety Requirements

In the event of a fire emergency involving Services Routers and other network equipment, the safety of people is the primary concern. Establish procedures for protecting people in the event of a fire emergency, provide safety training, and properly provision fire-control equipment and fire extinguishers.

In addition, establish procedures to protect your equipment in the event of a fire emergency. Juniper Networks products must be installed in an environment suitable for electronic equipment. We recommend that fire suppression equipment be available in the event of a fire in the vicinity of the equipment, and that all local fire, safety, and electrical codes and ordinances be observed when you are installing and operating your equipment.

Fire Suppression

In the event of an electrical hazard or an electrical fire, first unplug the power cord. (For shutdown instructions, see “Powering a Services Router On and Off” on page 127.)