MX240 Ethernet Services Router Hardware Guide

Figure 61: Grounding Cable Lug

CAUTION: Before router installation begins, a licensed electrician must attach a cable lug to the grounding and power cables that you supply. A cable with an incorrectly attached lug can damage the router.

NOTE: The same cable lug is used for the DC power cables.

Grouding Cable Specification

The grounding cable that you provide must meet the specifications in

Table 27 on page 166.

Table 27: Grounding Cable Specifications

Cable Type

Quantity and Specification

Grounding

One 6-AWG (13.3 mm2), minimum 60°C wire, or as permitted by the local

 

code

DC Power Specifications and Requirements

DC Power Specifications on page 166

Power Consumption for DC-Powered Routers on page 167

DC Power Circuit Breaker Specifications on page 169

DC Power Cable Specifications on page 170

DC Power Specifications

DC Power System Electrical Specifications on page 167

DC Power Supply Electrical Specifications on page 167

166DC Power Specifications and Requirements