DEFINITY Enterprise Communications Server Release 6 | Issue 3 |
Installation and Test for Compact Modular Cabinets | May 1998 |
|
|
2Installation Completion and Cable Pinouts
Perform System Administration | Page |
Enable Alarm Origination to INADS
No External Modem Installed (or No Alarm Origination to INADS)
1.Enter change system-parameters maintenance and press Enter.
2.Enter n in the Alarm Origination Activated to OSS Numbers field and press
Enter.
3.For some software releases, enable Cleared Alarm Notification and Restart Notification before the submitting the form.
External Modem Installed
1.Enter change system-parameters maintenance and press Enter.
2.Enter y in the Alarm Origination Activated to OSS Numbers field and press
Enter.
3.For some software releases, enable Cleared Alarm Notification and Restart Notification before the submitting the form.
4.Be sure the system is part of the INADS database by calling the INADS Database Administrator at the Technical Service Center (TSC). Verify that INADS can dial into the system and that the system can dial out to INADS.
As part of the system registration process, the INADS Database Administrator enables Alarm Origination and customer options.
NOTE:
When calling from a remote modem, you may need to disable error
correction to allow the modems to connect successfully. For example, the AT&T Paradyne KeepInTouch®modem may require the “AT\n0” command.
5.Log off and log back in.
Place a Test Call
1.From any telephone connected to a digital line circuit pack, call any nearby telephone connected to an analog line circuit pack.
2.Verify that the dial tone, ringing pattern, and talk path are acceptable.
3.Place a call through the Central Office (outside call) to any nearby telephone. Verify that the dial tone, ringing pattern, and talk path are acceptable.